Industrial DIN Rail Temperature Transmitter NCS-TT106H-R With HART Protocol
Parameter |
Value |
Input Signal |
Resistance: PT100, CU50, CU100, 0~500Ω, 0~4000Ω Thermocouple: B, E, J, N, K, R, S, T Voltage signal: -100mV~100mV |
Channel |
Double |
RTD Wiring |
2-wire, 3-wire, 4-wire |
Bus Power |
11~35 VDC Current consumption (static): ≤14mA |
Isolation |
1000VAC |
Working Temperature |
-40℃~85℃ |
Humidity Range |
0%~95%RH |
Start Time |
≤5s |
Refresh Time |
0.8s-1.3s |
EMC |
GB/T 18268.1-2010 |
Protection |
IP20(terminal IP00) |
Signal Type |
Suggested Range (℃) |
Accuracy(25℃) |
Resistance |
0~500Ω, 0~4000Ω |
±0.04Ω ±0.35Ω |
PT100 |
-200~850℃ |
±0.15℃ |
PT1000 |
-200~850℃ |
±0.15℃ |
CU50 |
-50~150℃ |
±0.15℃ |
CU100 |
-50~150℃ |
±0.1℃ |
mV |
-100mV~100mV |
0.025mV |
B |
500℃~1810℃ |
±0.77℃ |
E |
-200℃~1000℃ |
±0.2℃ |
J |
-190℃~1200℃ |
±0.35℃ |
K |
-200℃~1372℃ |
±0.4℃ |
N |
-190℃~1300℃ |
±0.5℃ |
R |
0℃~1768℃ |
±0.75℃ |
S |
0℃~1768℃ |
±0.7℃ |
T |
-200℃~400℃ |
±0.35℃ |
Send Inquiry to This Supplier
You May Also Like
-
MODBUS RTU to FF DIN Rail Mounting GatewayUS$ 330 - 360MOQ: 1 Piece
-
G1013 HART Protocol (4-20mA) to FF Protocol Smart Gateway (Converter)US$ 369 - 399MOQ: 1 Piece
-
Communication Protocol Gateway ---For RS485 to Profibus PA Communication BoardUS$ 160 - 168MOQ: 1 Piece
-
G1100 WirelessHART Intelligent Gateway Establish ,manage, Mainten of WirelessHART Net WorkUS$ 3000 - 3300MOQ: 1 Piece
-
Modbus to HART Built-in Communication ModuleUS$ 80 - 100MOQ: 1 Piece
-
Modbus RTU to Fieldbus FF Built-in ModuleUS$ 200 - 230MOQ: 1 Piece
-
Protocol Converter Module---MODBUS to Profibus PA (RS232)US$ 200 - 230MOQ: 1 Piece
-
USB or Serial Port HART Modem Used for HART ConfigurationUS$ 189 - 199MOQ: 1 Piece
-
Wireless Adapter/WirelessHART Adapter Connect 4-20mA,HART and Modbus Device to WirelessHARTUS$ 500 - 520MOQ: 1 Piece
-
Digital Capacitance Sensor Gauge Pressure Transmitter With HART ProtocolUS$ 350 - 360MOQ: 1 Piece