RHH/RHW-2/USE-2 ALUMINUM CONDUCTOR
Product Spotlights
Application
Type RHH or RHW-2 or USE-2 conductors are used with conduit as specified in the National Electrical Code. When used as Type USE-2, conductors are suitable for use as underground service entrance conductors for direct burial at conductor temperatures not to exceed 90°C. When used as RHW-2 or USE-2, conductor temperatures shall not exceed 90°C in wet or dry locations. Voltage rating for RHW-2 or RHH or USE-2 conductors is 600 volts.
Construction
Type RHH or RHW-2 or USE-2 conductors are AA-8000 series aluminum alloy, compact stranded. The insulation is an abrasion, moisture, heat and sunlight-resistant black cross-linked polyethylene (XLP). CT rated available upon request sizes 1/0 and larger.
Features
● Conductor for reduced diameter
● General purpose use in construction:
● Residential
● Commercial
● Institutional
● Industrial construction
Standards & References
Type RHH or RHW-2 or USE-2 conductors comply with the following:
● ASTM B-800 and B-801
● UL 44 for RHH or RHW-2
● UL 854 for USE-2
● National Electrical Code, NFPA 70, 2011 Edition
● NEMA WC-70 Construction Requirements
● RoHS/Reach Compliant
High reliability
Super high pressure
Less maintenance
Technical Parameter
RHH/RHW-2/USE-2 Aluminium Conductor
| Conductor | Insulation thickness | Nominal O.D. | Approx. weight | Ampacity+ | |||||
| AWG/kcmil | Min. No. | mm | mils | mm | kg/km | 60℃ | 75℃ | 90℃ | |
| 6 | 7 | 1.52 | 60 | 7.3 | 67 | 40 | 50 | 60 | |
| 4 | 7 | 1.52 | 60 | 8.5 | 95 | 55 | 65 | 75 | |
| 2 | 7 | 1.52 | 60 | 9.9 | 136 | 75 | 90 | 100 | |
| 1 | 18 | 2.03 | 80 | 11.7 | 185 | 85 | 100 | 115 | |
| 1/0 | 18 | 2.03 | 80 | 12.6 | 222 | 100 | 120 | 135 | |
| 2/0 | 18 | 2.03 | 80 | 13.6 | 267 | 115 | 135 | 150 | |
| 3/0 | 18 | 2.03 | 80 | 14.8 | 324 | 130 | 155 | 175 | |
| 4/0 | 18 | 2.03 | 80 | 16.1 | 394 | 150 | 180 | 205 | |
| 250 | 35 | 2.41 | 95 | 18.0 | 480 | 170 | 205 | 230 | |
| 300 | 35 | 2.41 | 95 | 19.3 | 560 | 190 | 230 | 255 | |
| 350 | 35 | 2.41 | 95 | 20.5 | 639 | 210 | 250 | 280 | |
| 400 | 35 | 2.41 | 95 | 21.6 | 719 | 225 | 270 | 305 | |
| 500 | 35 | 2.41 | 95 | 23.5 | 874 | 260 | 310 | 350 | |
| 600 | 58 | 2.79 | 110 | 26.2 | 1065 | 285 | 340 | 385 | |
| 700 | 58 | 2.79 | 110 | 27.9 | 1221 | 310 | 375 | 420 | |
| 750 | 58 | 2.79 | 110 | 28.6 | 1297 | 320 | 385 | 435 | |
| 900 | 58 | 2.79 | 110 | 31.0 | 1529 | 355 | 425 | 480 | |
| 1000 | 58 | 2.79 | 110 | 32.5 | 1685 | 375 | 445 | 500 | |
+Allowable ampacities shown are for general use as specified by the 2014 Edition of the National Electrical Code Sections 310.15 and 240.4(D)
Unless the equipment is marked for use at higher temperatures the conductor shall be limited to the following per NEC 110.14(C):
75℃ - When terminated to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
90℃ - THHN dry locations and THWN-2 wet or dry locations for ampacity adjustment purposes using NEC section 310.15.
Send Inquiry to This Supplier
You May Also Like
-
Rated Voltage 0.6/1 kV Reel Cable for Drilling RigsNegotiableMOQ: 3000 Meters
-
Rubber Insulation Cables And WiresNegotiableMOQ: 3000 Meters
-
MC-XHHW-2 ALUMINUM (AA-8000)NegotiableMOQ: 3000 Meters
-
TECK90 INTERLOCKED ARMOUR CABLESNegotiableMOQ: 3000 Meters
-
600V Service CableNegotiableMOQ: 3000 Meters
-
Factory Direct ACSR Bare Conductor - Customizable Sizes With Fast DeliveryUS$ 0.35MOQ: 1000 Meters
-
All Aluminium Alloy Conductor (AAAC) - Full Series Standard Compliant Bare Overhead Transmission Line WireUS$ 0.38MOQ: 3000 Meters
-
0.6/1kV XLPE Insulated Aerial Bunch Cable (ABC Cable) With Aluminum Conductor for Overhead Power DistributionUS$ 0.35MOQ: 3000 Meters
-
Hot-Dip Galvanized Steel Strand Guy Wire for Overhead Power LineUS$ 0.25MOQ: 3000 Meters
-
Aluminum-Clad Steel Strand for Overhead Transmission LineUS$ 0.35MOQ: 3000 Meters