Medium Voltage Cables UNE HD 620 S3
Product Spotlights
Halogen-free low-smoke, UV-resistant, supports multi-scenario laying, perfectly meets European distribution network requirements.
Application
Medium voltage cables for distribution networks; also for connection to generation units and plant and process connection. To be laid directly in ground, outdoors, indoors and in cable ducts.
Construction
● Conductor: Aluminum or copper, class 2,circular compacted conductors
● Conductor screen: Non-metallic,semi-conducting compound
● Insulation: Cross - Linked Polyethylene XLPE,Nominal Insulation Thickness or Reduced Insulation Thickness
● Insulation screen: Non-metallic,semi-conducting compound
● Metallic screen: Aluminium plastic tape (AL/PET)
● Outer sheath: Polyolefin,PO (DMZ1,DMZ2,LSOH,LSZH),Black or Red
Chaircteritics
Good electrical and mechanical properties. Low factor dielectric loss, high insulation resistance. The PO outer sheath allows adequate resistance to UV and abrasion.
Different CPR levels require different structures and materials.
Specification
IEC 60502-2 Power Cables with Extruded Insulation and Their Accessories for Rated Voltages from 1 kV (Um=1.2kV) up to 30kV (Um=36kV) - Part 2:Cables for Rated Voltages of 6kV (Um=7.2kV) and 30 kV (Um=36kV)
HD 620 S1 Distribution Cables with Extruded Insulation for Rated Voltages from 3.6/6(7.2) kV to 20.8/36(42) kV
HD 620 S2 Distribution Cables with Extruded Insulation for Rated Voltages from 3.6/6(7.2) kV to 20.8/36(42) kV
UNE 211620 Cables eléctricos de distribución con aislamiento extruido, de tensión asignada desde 3.6/6 (7.2) kV hasta 20.8/36 (42) kV inclusive Cables unipolares y unipolares reunidos con aislamiento de XLPE Cables con pantalla de tubo de aluminio y cubierta de compuesto de poliolefina (tipos 10E-6, 10E-7, 10E-8 y 10E-9)
High reliability
Super high pressure
Less maintenance
POWER CABLE RH5Z1
POWER CABLE RH5Z1
| No. of Cores and Nominal Cross Section | Nominal Insulation Thickness | Nominal AL/PET tape thickness |
Nominal Sheath Thickness |
Approx. Overall Diameter | Approx. Weight | Max. D.C. Resistance of Conductor at 20℃ |
| Al | Al | |||||
| mm² | mm | mm | mm | mm | kg/km | Ω/km |
| 12/20kV Reduced Insulation Thickness | ||||||
| 1X50 | 4.9 | 0.3 | 2.75 | 28.1 | 817 | 0.641 |
| 1X95 | 4.9 | 0.3 | 2.75 | 31.6 | 1067 | 0.320 |
| 1X150 | 4.9 | 0.3 | 2.75 | 34.3 | 1298 | 0.206 |
| 1X185 | 4.9 | 0.3 | 2.75 | 36.0 | 1456 | 0.164 |
| 1X240 | 4.9 | 0.3 | 2.75 | 38.3 | 1693 | 0.125 |
| 1X400 | 4.9 | 0.3 | 2.75 | 43.2 | 2263 | 0.0778 |
| 1X630 | 4.9 | 0.3 | 2.75 | 50.3 | 3191 | 0.0469 |
| 18/30kV Reduced Insulation Thickness | ||||||
| 1X50 | 7.25 | 0.3 | 2.75 | 32.8 | 1055 | 0.641 |
| 1X95 | 7.25 | 0.3 | 2.75 | 36.3 | 1329 | 0.320 |
| 1X150 | 7.25 | 0.3 | 2.75 | 39.0 | 1579 | 0.206 |
| 1X185 | 7.25 | 0.3 | 2.75 | 40.7 | 1748 | 0.164 |
| 1X240 | 7.25 | 0.3 | 2.75 | 43.0 | 2001 | 0.125 |
| 1X400 | 7.25 | 0.3 | 2.75 | 47.9 | 2604 | 0.0778 |
| 1X630 | 7.25 | 0.3 | 2.75 | 55.0 | 3582 | 0.0469 |
Send Inquiry to This Supplier
You May Also Like
-
CU(AL)/XLPE/CWS/SWA/PVC Three Core 6.6~33kVNegotiableMOQ: 3000 Meters
-
CU(AL)/XLPE/CWS/PVC Three Core 6.6~33kVNegotiableMOQ: 3000 Meters
-
CU(AL)/XLPE/CWS/AWA/PVC Single Core 6.6~33kVNegotiableMOQ: 3000 Meters
-
CU(AL)/XLPE/CWS/PVC Single Core 6.6~33kVNegotiableMOQ: 3000 Meters
-
NAYY (VLV)NegotiableMOQ: 3000 Meters
-
NA2XBY (YJLV22) 0.6-1kVNegotiableMOQ: 3000 Meters
-
NA2XRY (YJLV32) 0.6-1kVNegotiableMOQ: 3000 Meters
-
NA2XY (YJLV) 0.6-1kVNegotiableMOQ: 3000 Meters
-
NAYBY (VLV22)NegotiableMOQ: 3000 Meters
-
NAYRY (VLV32)NegotiableMOQ: 3000 Meters