Home > Light Industry & Daily Use > Disposable Products > Disposable Sanitary Products > 180V Single Channle Audio Signal Lightning Protector

180V Single Channle Audio Signal Lightning Protector

180V Single Channle Audio Signal Lightning Protector photo-1
180V Single Channle Audio Signal Lightning Protector photo-2
Negotiable MOQ: 1 Meter (Price negotiable depending on order volume and customization)
Key Specifications
Get Latest Price
Brand Name:
ANSUN
Place of Origin:
China
Model Number:
AS180R
Payment & Shipping
Payment Methods:
Port of Shipment:
China
Delivery Detail:
7 days
Brand Name ANSUN
Place of Origin China
Model Number AS180R

Safety precautions:

a) When SPD is installed in final system, it must achieve all the requirements of GB4943 (EN60950, IEC60950) standard;

b)  The equipment has to be installed by authorized professional person,  to avoid incorrect installation or application to influence the normal working and lightning protection of devices

 

Application

Mainly used to protect the devices from lightning strike and over-voltage damage, which transmit the audio signal by twisted pair

Such as telephone, fax machine, MODEM, exchange, ADSL, ISDN, etc

 

Features

1)  Multi stage protective circuit, big discharge current capacity, low residual voltage

2)  International famous core component brand

3)  Low insertion loss, quick response

4)  Precise limiting voltage

5)  19 inch Integrated 16 channels audio signal SPD box

6)  Stable performance, reliable work

7)  Easy installation

 

Specification

 

Model

AS180R

Nominal operating Voltage

180V

Nominal discharge current(kA)

3kA

Max discharge current(kA)

5kA

Protection level(Up)

Line to line

≤30V

Line to ground

≤250V

Response time

≤1ns

Transmission rate

10Mbps

Insertion loss

≤0.5dB

Interface type

RJ11

Protection Channel

1

Protection form

2/3-4/5

Dimension(mm)

68 * 25 * 25

Protection Level

IP20

Installation

Series, 19inch rack-mounted

Working conditions

Temperature:40~+85℃; Relative humidity:≤95(25); Elevation≤3km

Note: For latest information, please contact ANSUN company

 

 Installation and wiring

a)   SPD is connected by series between protected devices and signal path

b)   The input side of SPD connects to signal path, output side connects closely to protected device,

c)   To connect ground line of SPD to lightning protection system ground device, lower 

connecting wire is better, within 1m

 

Product maintenance

1) The product does not need to be maintained specially, but to inspect at fixed period, especially

     before and during thunderstorm season.

2)  Once there is a failure during system operation, please remove the SPD device at first, if the

system can operate normally, the device is broken

Send Inquiry to This Supplier

Message
0/5000

Want the best price? Post an RFQ now!
Business Type
Trading Company
Total Employees
101 - 200 People
Main Markets
North America, South America, Eastern Europe
Location
Yan'an, Shaanxi, China

Recommended Categories

Explore top categories and find suppliers for your specific needs