- China Manufacturer with main products:Earth Fault Indicator ,Cable Fault Indicator ,Overhead Line Ground Fault Indicator ,Short Circuit and Earth Fault Indicator ,Cable Temperature and Faults Sensor ,Industrial Dehumidifier ,Temperature and Humidity Controller ,Fault Passage Indicator ,Remote communication terminal ,Smart grid system
Home > Products > Short Circuit and Earth Fault Indicator > New Design SNV-EKL4 v2.1 Earth fault and short circuit indicator
New Design SNV-EKL4 v2.1 Earth fault and short circuit indicator
- 100000 Piece / Pieces per Month
- Shenzhen
- T/T L/C
- 7 days
- Grounding fault indicator SNV-EFI V1
- How do Overhead Line Fault Indicator FPI Work?
- Cable short circuit and grounding fault indicator SNV-EKL3.2
- Overhead line fault passsage indicator working principle
- New type digital Intelligent overhead line type cable short circuit and ground fault indicator for power distribution line SFI
- SNV-EFI earth fault indicator electric power sensor substation
Product Details
Brand Name: | SNOVA | Place of Origin: | China | Model Number: | SNV-EKL4 v2.1 |
Product Description
SNV-EKL4 v2.1 Earth fault and short circuit indicator
Type: cable type,surface mounted,battery 19000mHA
Description
SNV-EKL4 v2.1, Earth fault and short circuit indicator, it Widely used in various ring cabinets, high/ Medium or low -voltage switch gear and cable branch box in power system, can accurately and reliably detect the fault section and fault type of power grid in the Low/medium voltage network. The use of cable type grounding fault and short circuit indicator is an efficient way to check cable fault, and is an effective way to improve the operation level of distribution network and the efficiency of fault handling. The design uses electromagnetic induction, and single chip microcomputer control technology to make fault alarm with high accuracy and strong anti-interference ability.
Equipped with fault remote transmission port, suitable for distribution network automation; Battery low power alarm indication; Low-power consumption design, high-capacity lithium battery power supply, long battery life (more than 10 years); external structure using card or lock design, the whole machine is easy to load and unload.
Function character:
1) Intelligent detection of ground fault and through the corresponding LED (I0),on the display unit to indicate fault.
2) Intelligent detection of short circuit fault of phase to phase and through the corresponding LED (L1, L2,L3),on the display unit to indicate fault.
3)Display unit designed with button, it is convenient for reset or test.
4)The pulse width time of fault current (Response time) can be set to prevent incorrect fault indication caused by surge current through modbus of RS485 port.
5)It can reset and detect the remote fault indication device remotely by SCADA or press key.
6)It can provide switch volume for external devices through remote contact.
7)It can change the reset time after fault happen through Modbus of RS485 port. (when purchase, it need to tell factory to set,default 8hours).
8)Remote fault indicating can be made by external lamp.
9)Earth fault alarm current (40/50/60/70/80/100/120/250A)
Tripping current(350/400/450/500/550/600/650/700A),8-level can be settable through a DIP switch inside of the display unit.(optional).
10)Low battery display and alarm test through press the “Test/reset” key by 3seconds.
11) Battery can be changeable conveniently, Big capacity 19000mHA,D- Size, ER34615.
12) Sensor cable spec: NYAF,copper cable,(2x1.5㎟ ) ,7 meters length.
13) Support AC/DC power input, AC48-240V.
14) Support Automatic Low voltage reset, AC>30V.
Function description
1) Earth fault alarm indicating: when the earth fault sensor detected an earth fault current, and the current is bigger than equal to or equal to the setting value, then the earth fault sensor send a signal to display unit through electric cable. And the display unit will display the alarm signal, at same time, the earth fault LED will be blinking.
2) Short circuit indicating: when the short circuit sensor detected an over current, and the current is bigger than equal to or equal to the setting value, then the short circuit sensor send a signal to display unit through electric cable. And the display unit will display the alarm signal, at same time, corresponding LED (L1, L2,L3) will be blinking to indicate the fault.
3) Battery low voltage alarm indicating: the display unit use the battery to supply power. When we press the “Test” button,3seconds time: If the battery voltage is lower than the working voltage Min.2.5V, then the Battery Level Led will be blinking 5 times; If battery voltage is normal, then only blink 1 times.
4)Automatic time reset: After the indicator alarm the fault, if there are without manual reset it, when the time reach our reset time setting, indicator will automatically reset.
5) Manual reset: After the indicator alarm the fault, user can press the button “ reset/test” in a short time to reset it.
6)Automatic Low voltage reset: Through inputting AC30-240V power to the pin 14,15 on the PCB in the display unit, when indicating fault, at same the voltage powered off. when the voltage recover and power on again, then indicator will be reset immediately via low voltage.
7) Out side AC110-240V power supply energy for display unit. It use the same as voltage of the “voltage reset” via pin 14,15.8) Remote(Scada) reset/test: through short connect the pin 12,13 then indicator will be run the reset/test process, and Led will be blinking.
*Connect the pin 12,13 by short time(1second), then it will be reset indicator.
* connect the pin 12,13 by a long time(3seconds), then it will be test indicator.
9)Remote indicating: Through connect the pin 16,17 to the external lamp , then it will be indicate fault when any phase alarm fault.
10)Remote to SCADA system by Modbus: connect pin 18 (A), 19 (B).
Define and connect of terminal inside box.
Pin 1-2: L1, Short circuit sensor connect, CT L1
Pin 3-4: L2, Short circuit sensor connect, CT L2
Pin 5-6: L3, Short circuit sensor connect, CT L3
Pin 7-8: I0, Earth fault sensor connect, CT I0
Pin 9-10: NC relay ,
Pin 9-11: NO relay
Pin 12-13 : Remote Reset/ test.( connect 1second for Reset; 3second for Test)
Pin 14-15: power supply(AC110-240V), and voltage reset (AC30-240V)
Pin 16(-)-17(+): External indicating LED
Pin 18-19: Modbus communicate with SCADA system of PC.
Operation description
1) Test: Before installation, press the display panel’s “ reset/test “ button, 3 second. Then the indicator will go into the self- checking state:
--Battery Level voltage led flash 1 times, (if the battery low voltage, it flash 5 times);
-- Fault indicating led flash, after 10 second, display unit will recover back the normal state. Or shortly press the “ reset/test” button to finish the self-checking state.
2) Clean Alarm: After fault indicating, when we solve the line or device problem, we can reset the indicator to Clean alarm as below three way:
1. shortly press the “ reset/test” button to clean alarm,
2. remote (scada) reset through connect Pin 3,4 by scada or key-switch control
3. wait it automatically reset after reset time setting value.
4. Voltage reset: when display unit voltage OFF , then voltage ON again.
Note: in order to use this Voltage reset feature, the 110-240Vac voltage must disappear when the fault occurs, i.e. it must be cut off by the MV circuit breaker that breaks the faulty line, otherwise the EFI will not operate voltage reset.
Working characteristics:
When the Earth line occurs fault current, and the fault current is above than the trip current level,and fault current is running a delay time above that “response time” level. Then indicator will be indicating fault. After a “reset time” EFI will be reset automatically.
Installation
1) Dimension and installation:
Display unit outside size: 192x90x60mm
Surface mounted on the wall or cabinet bolts M4. Hole distance position: 50mm x 178mm.
Cable gland (M20x1.5): fit for 6-12mm cable.
1) sensor installation
First uninstall one screw off sensor, then install sensor cross through the cable, and screw on again. Then use zip-belt to fixed sensor with cable.
About Earth fault sensor need to round the 3 phases cable conductor together (if have phase N,then directly mounted on phase N cable). And tighten it with belt, and the cable grounding line must insert back the sensor, and tighten it avoid the loose and fall down. As below:
Fault indicator packing list
1. Display unit 1Pcs
2. Earth fault sensor with 7meters cable 1Pcs
3. Short circuit sensor with 7meters cable 3pcs
4. User manual 1Pcs
5. SNV-Lamp3, External Lamp(Optional) 1pcs
Contact Us
- Zhuhai City Snova Technology Co., LTD
- Contact nameAndrewmao
- Phone86-13570657698-8621065
- AddressXiangzhou district Zhuhai,Guangdong
- SNOVA Technology Sell Intelligent Fault Circuit Indicator
- 10KV-138KV Overhead Line fault passage indicator with remote comunication
- China factory supplier Power Accessories
- Fault Indicator Remote Wireless Communication Terminal
- Cable short circuit and grounding fault indicator SNV-EKL3.2
- Control PDA for fault locator
- Electric Handcart and Ground Knife Integrated Protection device
- Industrial intelligent dehumidifier for distribution cabinet
- Remote Control PDA of Overhead Line Fault Indicator
- New Design SNV-EKL4 v2.1 Earth fault and short circuit indicator
- Overhead line fault passsage indicator working principle
- Factory Customization Short Circuit Indicator High Voltage Fault Indicator
- Factory Customization Short Circuit Indicator High Voltage Fault Indicator
- Smart Gird Computer System for Fault Indicator
- Underground indicators Earth fault indicator for smart grid SNV-EFI
- SNV-EKL3.2 Earth fault and short circuit indicator
- SNV-EFI 3.0Smart Earth fault indicator with LCD disply
- Hot Sell for DIstribution Network ,current power fault location SNV-EKL3.2
- Flag type Overhead type Short circuit &Ground Fault Indicator
- How do Overhead Line Fault Indicator FPI Work?
- Grounding Faul Indicator RTU
- Overhead Line fault indicator for Generator, Transformer, Cables, Loads
- SNV-EFI earth fault indicator electric power sensor substation
- Overhead Line Communication fault passage indicator
Popular Searches
Find Similar Products By Category
- Electrical Equipment & Supplies > Power Accessories
- Buy on GoldSupplier.com
- How to Buy
- Browse by Catagories
- Browse by Hot Regoins
- Private Sourcing Events
- Sell on GoldSupplier.com
- How to Sell
- Post Products
- Manage Products
- Manage Groups
- About
- About Us
- Link to Us
- Contact Us
- Sitemap
- Please Enter your Email Address
- Please enter the content for your inquiry.
We will find the most reliable suppliers for you according to your description.
Send Now-
Andrewmao
Welcome to my shop! Glad to serve you!Please send your question!
Your message has exceeded the limit.
Your message has exceeded the limit.
-
-
Your inquiry content must be between 20 to 5000 characters.Send Now.
-
Please input the mailbox.
-