Modbus events are derived from SPA events. With a few exceptions, SPA events
update binary points in the DI and the packed HR area. Simultaneously, a
corresponding Modbus event record is generated. The event record contains the
Modbus DI/CO data point address and the value to which the point has changed (0
or 1). SPA events lacking a corresponding DI/CO data point are shown as SPA
channel and event code (informative event) in the event record. The maximum
capacity of the Modbus event buffer is 99 events. The time stamp of Modbus events
is extended to contain complete information, from date to millisecond.
To read an event record:
1. Write a preset single register command (function 06) to HR671 using a selection
code as data value.
2. Read the selected fault record (function 04) from HR672, register count 8.
Alternatively, a fault record can be read using one command (function 23) only.
Selection code 1: reading the oldest unread record
Status register 3 (HR403) informs whether there are unread event records (see
Fig. 5.1.15.1.-2). If there is one or several unread event records, the master can read
the contents using selection code 1.
The event record contains a sequence number which makes it possible for the master
to determine whether one or several unread event records have been deleted due to
overflow by comparing it to the sequence number of the previously read event
record.
The slave keeps track of which event record is currently the oldest unread. The
master can continue reading event records for as long as Status register 3 indicates
that there are unread records.
* Special case 1: If there are no unread event records, the contents of the last read
record is returned. If the buffer is empty, however, the registers contain only
zeros. This is the only time when sequence number zero appears.
* Special case 2: If the master tries to read the next unread event record without
entering selection code 1 again, the contents of the last read record is returned.
Send Inquiry to This Supplier
You May Also Like
-
PFSK160A 3BSE009514R1 ABB Online Hot Sale of Robot System Spare PartsUS$ 113 - 166MOQ: 100 Pounds
-
PFSK162 3BSE015088R1 ABB Functional Module Spare PartsUS$ 100 - 260MOQ: 100 Pounds
-
PFSK164 3BSE021180R1 ABB DSP Signal Processing ModuleUS$ 113 - 600MOQ: 100 Pounds
-
PFTL101A 2.0KN PFTL101B 2.0KN ABB Spare Parts for Tension Sensor AmplifierUS$ 100 - 200MOQ: 100 Pounds
-
PFTL101B-5.0KN/20KN 3BSE004203R1 ABB Supply of Spare Parts for Tension Controller SystemUS$ 190 - 200MOQ: 100 Pounds
-
PFTL201C 10KN/20KN/50KN ABB Tension Controller HeadUS$ 10 - 166MOQ: 100 Pounds
-
PFTL201D 10KN/20KN/50KN ABB Weighing Pressure SensorUS$ 165 - 166MOQ: 100 Pounds
-
PFTL201DE 10KN/20KN/30KN ABB Tension Sensor Measuring SystemUS$ 100 - 200MOQ: 100 Pounds
-
PFTL301E 1.0KN 3BSE019050R1000 ABB Tension Sensor Clamp EquipmentUS$ 100 - 200MOQ: 100 Pounds
-
PM150V08 3BSE009598R1 ABB Industrial Control Automation Controller in StockUS$ 100 - 200MOQ: 100 Pounds