Home > Electrical & Electronics > Power Transmission & Transformer > Transformer > TKJB-1200 Six Phase Universal Secondary Current Injection Relay Test

TKJB-1200 Six Phase Universal Secondary Current Injection Relay Test

TKJB-1200 Six Phase Universal Secondary Current Injection Relay Test photo-1
Negotiable MOQ: 1 Piece (Price negotiable depending on order volume and customization)
Key Specifications
Get Latest Price
Brand Name:
GDMK
Place of Origin:
China
Model Number:
TKJB
Payment & Shipping
Payment Methods:
Port of Shipment:
China
Delivery Detail:
Delivery time depends on order quantity.
Brand Name GDMK
Place of Origin China
Model Number TKJB
Product Introduction

TKJB - 1200 Six phase voltage and six phase current can be output, which has made it is possiable to be any combition, such as the output mode of the combination of conventional four phase current and three-phase current, six phase voltage mode, six phase current mode and 12 phase output mode. It not only can be compatible with the traditional way of various tests, but also can conveniently carry out differential test of three-phase transformer.



 
Product Characteristics
  • 1、Meet all field test requirements.The Microcomputer relay protection tester is a standard of six phase current six phase voltage output at the same time the current a/phase 30 voltage125V/phase.Six - phase current in parallel up to 180A.It can not only test the traditional relays and protection devices but also test the modern microcomputer protection especially the transformer differential protection and backup self-switching device the test is more convenient and perfect.

  • 2、All kinds of technical indexes have reached the standard of DL/ t624-1997 "technical conditions of microcomputer test equipment for relay protection" issued by the ministry of electric power.

  • 3、Classic WindowsXP operation interface man-machine interface friendly easy and quick to operate;The high-performance embedded industrial control computer and 8.4-inch TFT true-color display with a resolution of 800×600 provide rich and intuitive information including the current working status of the device and various help information.

  • 4、The native Windows XP system with recovery function to avoid illegal shutdown or misoperation caused by the system crash.

  • 5、The device has an ultra-thin industrial The keyboard and a photoelectric mouse that handles everything just like a PC.

  • 6、The main control board adopts DSP+FPGA structure and 16-bit DAC output which can generate high-density sinusoidal wave of 2000 points per week for the basic wave greatly improving the quality of waveform and improving the precision of tester.

  • 7、High-fidelity linear power amplifier ensures the accuracy of small current and the stability of large current.

  • 8、The Microcomputer relay protection tester with USB interface and PC communication directly without any connection easy to use.

  • 9、Connect to laptop (optional) to run.Laptop computer and industrial computer use the same set of software no need to learn how to operate.

  • 10、It is equipped with the independent auxiliary voltage source output the output voltage is 110V(1A) and 220V(0.6a) respectively.To be used by relays or protective devices that require dc working power.

  • 11、With the function of software self-calibration it avoids the need to open the chassis and adjust the potentiometer to calibrate the precision thus greatly improving the stability of the precision.

Product Parameters
Alternating current source
Amplitude range6×(0 ~ 30A)/ phase;Accuracy: 0.5%
Output maximum of six phase current in

parallel

180A
Long-term permissible operating value of

phase current

10A
Power300 va/phase
Maximum power in six phase parallel

connection

900VA
Permissible operating time for maximum

output in six phase parallel

10s
Frequency range0 ~ 1000 Hz;Accuracy: 0.001 Hz
Harmonic frequency2 ~ 20 times、Phase: 0 ~ 360°、Accuracy: 0.1 °
Direct current source
amplitude20A/phase
Power300VA/phase
Precision0.5%
Ac voltage source
Amplitude range6 x (0 ~ 125 V)、Accuracy: 0.5%
Line voltage range0~250V
Voltage output power70VA/100VA
Frequency range0 ~ 1000 Hz;Accuracy: 0.001 Hz
Harmonic frequency2 ~ 20 times、Phase: 0 ~ 360°、Accuracy: 0.1 °
Dc voltage source
Phase Voltage output amplitude0~±150V
Precision0.5%
Line Voltage output amplitude0~±300V
Voltage output power90VA/180VA
The switch quantity terminals
Switch input terminal8 pairs
The empty contacts1 ~ 20mA 24V Device internal active output
Potential flip0 ~ 6VDC is low level;15 ~ 250VDC is high level
Switch output terminal4 pairs empty contacts blocking capacity: 110V/2A 220V/1A
Time Measuring range
The scope of1ms~9999s
Accuracy of measurement1ms
volumeThe weight of the
volume455×530×220mm3
Weightabout 30 kg
The power supply
AC220V±10% ; 50Hz,15A


Product Tags: Secondary Current Injection test set , universal relay test set , protection relay test set

Send Inquiry to This Supplier

Message
0/5000
Want the best price? Post an RFQ now!
Business Type
Manufacturer
Year Established
2014
Main Markets
Southeast Asia

Recommended Categories

Explore top categories and find suppliers for your specific needs