Home > Electrical & Electronics > Power Transmission & Transformer > Transformer > TKJB-802 Secondary Current Injection Test Set Three Phase Relay Test

TKJB-802 Secondary Current Injection Test Set Three Phase Relay Test

TKJB-802 Secondary Current Injection Test Set Three Phase Relay Test photo-1
Negotiable MOQ: 1 Piece (Price negotiable depending on order volume and customization)
Key Specifications
Get Latest Price
Brand Name:
GDMK
Place of Origin:
China
Model Number:
TKJB-802
Payment & Shipping
Payment Methods:
Port of Shipment:
China
Delivery Detail:
Delivery time depends on order quantity.
Brand Name GDMK
Place of Origin China
Model Number TKJB-802
Product Introduction

  High-Performance Industrial Control Computer

High performance Industrial control computer is adopted as the controlling computer, through which you can run the windows operating system directly. 6.4"TFT true color LCD display, tracking ball and optimized keyboard are allocated on the faceplate of this tester, which can be used without the external mouse and keyboard. USB interface, 10-100M net mouth and serial communication interface are located on the back plate of this tester, through which you can access data, communicate data and upgrade software conveniently.

The whole process and the result of the test will all be showed on the LCD. The English operational interface of the complete set is very friendly and convenient. The tracking ball and keyboard on the faceplate will implement the operation. The operation is simple and convenient, and is easy to be mastered. Operator only needs a little knowledge of computer.

Keyboard and mouse interface are also allocated on the faceplate. If you would like to use the external mouse and keyboard, through pluging them with corresponding interfaces, you can operate this tester just like operate a desk-top computer.


 

Product Characteristics
  • 1、Meet all field test requirements.The Microcomputer relay protection tester has the standard four phase voltage three phase current output voltage125V/phase phase current a / 40.Three-phase parallel connection up to 120A.It can be used not only for traditional relays and protection devices but also for modern microcomputer protection especially for transformer differential power protection and backup automatic switching device which makes the test more convenient and perfect.

  • 2、All kinds of technical indexes have reached the standard of DL/ t624-1997 "technical conditions of microcomputer test equipment for relay protection" issued by the ministry of electric power.

  • 3、Classic WindowsXP operation interface man-machine interface friendly easy and quick to operate;The high-performance embedded industrial control computer and 8.4-inch TFT true-color display with a resolution of 800×600 provide rich and intuitive information including the current working status of the device and various help information.

  • 4、Relay protection device (testerWindows XP) has built-in recovery function to avoid system crash caused by illegal shutdown or misoperation.

  • 5、Equipped with an ultra-thin industrial keyboard and photoelectric mouse it can complete various operations through the keyboard or mouse just like the operation of ordinary PC.

  • 6、The main control board adopts DSP+FPGA structure and 16-bit DAC output which can generate high-density sinusoidal wave of 2000 points per week for the basic wave greatly improving the quality of waveform and improving the precision of tester.

  • 7、High-fidelity linear power amplifier ensures the accuracy of small current and the stability of large current.

  • 8、Use USB interface to communicate directly with PC without any connection easy to use.

  • 9、Connect to laptop (optional) to run.Laptop computer and industrial computer use the same set of software no need to learn how to operate.

  • 10、It is equipped with the independent auxiliary voltage source output the output voltage is 110V(1A) and 220V(0.6a) respectively.To be used by relays or protective devices that require dc operating power.

  • 11、With the software self-calibration function it avoids the need to open the chassis and adjust the potentiometer to calibrate the precision thus greatly improving the stability of the precision.

Product Parameters
Alternating current source
Phase current output (RMS) 0 ~ 40A/ phase accuracy: 0.5%
Three-phase parallel output (RMS) 0 ~ 120A/ three parallel outputs with the same phase
Long-term permissible working value of

phase current (effective value)

10A
Maximum power output per phase 420VA
Maximum output power of three-phase

parallel current

900VA
The maximum allowable working time of

current output

10s
Frequency range 0 ~ 1000 Hz、Accuracy: 0.001 Hz
Harmonic frequency 2 ~ 20 times、Phase: 0 ~ 360°、Accuracy: 0.1 °
Direct current source
Output current 0 ~ ±30A/ phase、Accuracy: 0.5%
Ac voltage source
Phase voltage output (RMS) 0 ~ 125V/ phase accuracy: 0.5%
Line voltage output (RMS) 0~250V
Voltage output power 75VA/100VA
Frequency range 0 ~ 1000 Hz、Accuracy: 0.001 Hz
Harmonic frequency 2 ~ 20 times、Phase: 0 ~ 360°、Accuracy: 0.1 °
Dc voltage source
Phase Voltage output amplitude 0 ~ ±150V、Accuracy : 0.5%
Line Voltage output amplitude 0~±300V
Voltage output power 90VA/180VA
The switch quantity terminals
Switch input terminal 8 pairs
The empty contacts 1 ~ 20mA 24V Device internal active output
Potential flip 0 ~ 6VDC is low level ; 15 ~ 250VDC is high level
Switch output terminal 4 pairs empty contacts blocking capacity: 110V/2A 220V/1A
Time Measuring range
The scope of 1ms~9999s
Accuracy of measurement 1ms
volumeThe weight of the
volume 455×530×220mm3
Weight about30kg
The power supply
AC 220V±10% ; 50Hz ; 15A


Product Tags: secondary current injection tester , 3 Phase Relay Test Kit , secondary test current

Send Inquiry to This Supplier

Message
0/5000

Want the best price? Post an RFQ now!
Verified Business License
Business Type
Manufacturer
Year Established
2014
Main Markets
Southeast Asia

Recommended Categories

Explore top categories and find suppliers for your specific needs