Vlf High Voltage Very Low Frequency AC Hipot Tester
Vlf High Voltage Very Low Frequency AC Hipot Tester
General information:
VLF Test Sets from 30kV - 90kV with Sine Wave Output
VLF means 'Very Low Frequency' is used in AC hipot test for power cables, transformers, switchgear and other electrical apparatus.
A VLF hipot is just an AC output tester but with an output frequency of 0.1 Hz or lower rather than 50/60Hz. Although the frequency is very low, it is still an alternating current with polarity reversals every half cycle. At 0.1 Hz output, rather than 60Hz, it takes 600 times less current and power to apply an AC voltage to a capacitive load, like a long cable.
Features:
√ Adapts microprocessor controlled, can realize voltage set-up/down, measuring and protecting automatically. Manual intervention is allowable even during the auto voltage boosting.
√ Portable, easy to move.
√ Large LCD can display waveform clearly, and test report can be printed by built-in printer.
√ The data of current, voltage, and waveform can be sampled at HV side.
√ Over voltage protection: When the output is beyond the limitation, the control unit will shut itself down within 20ms.
√ Over current protection: high & low voltage double protection, the precision value of power off protection can be setting at HV side. When the current of LV side is exceeded rated, the control unit will shut itself down within 20ms.
√ HV output protection resistor is built in the booster, not need to connect outside resistor.
√ Adapting high & low voltage closed loop negative feedback control circuit, there is no capacitive rise effect during the output.
Specifications:
| Model | Output Voltage/Current (Peak) |
Load Capacity | Fuse | Control Unit | Booster | ||
| Net Dim. (cm) |
Net Wt (kg) |
Net Dim. (cm) |
Net Wt (kg) |
||||
| SXVLF-30/1.1 | 30KV/29mA | 0.1Hz ≤ 1.1uF | 8A | 28×37×22 | 4 | 33×18×34 | 25 |
| 0.05Hz ≤ 2.2uF | |||||||
| 0.02Hz ≤ 5.5uF | |||||||
| SXVLF-40/1.1 | 40KV/29mA | 0.1Hz ≤ 1.1uF | 8A |
28×37×22 | 4 | 35×20×36 | 45 |
| 0.05Hz ≤ 2.2uF | |||||||
| 0.02Hz ≤ 5.5uF | |||||||
| SXVLF-50/1.1 | 50KV/59mA | 0.1Hz ≤ 1.1uF | 10A |
28×37×22 | 4 | 37×24×39 | 45 |
| 0.05Hz ≤ 2.2uF | |||||||
| 0.02Hz ≤ 5.5uF | |||||||
| SXVLF-60/0.5 | 60KV/59mA | 0.1Hz ≤ 0.5uF | 20A |
28×37×22 | 4 | 33×18×34 33×18×34 |
25+45 |
| 0.05Hz ≤ 1.0uF | |||||||
| 0.02Hz ≤ 2.5uF | |||||||
| SXVLF-70/0.5 | 70KV/59mA | 0.1 Hz, ≤0.5µF | 20A |
28×37×22 | 4 | 33×18×34 35×20×36 |
25+45 |
| 0.05Hz, ≤1.0µF | |||||||
| 0.02Hz, ≤2.5µF | |||||||
| SXVLF-80/0.5 | 80KV/59mA | 0.1 Hz, ≤0.5µF | 20A | 28×37×22 | 4 | 33×18×34 37×24×39 |
25+45 |
| 0.05Hz, ≤1.0µF | |||||||
| 0.02Hz, ≤2.5µF | |||||||
| SXVLF-90/0.5 | 90KV/59mA | 0.1 Hz, ≤0.5µF | 20A |
28×37×22 | 4 | 33×20×35 37×24×39 |
30+45 |
| 0.05Hz, ≤1.0µF | |||||||
| 0.02Hz, ≤2.5µF | |||||||
√ Accuracy: 3%
√ Voltage +/- peak value error: ≤3%
√ Voltage waveform distortion: ≤5%
√ Working temperature: -10ºC+40ºC
√ Working humidity: ≤85%RH
Please contact us for further information. Sansion Power has a technically experienced expertise team to select correctly designed test set for you.
Send Inquiry to This Supplier
You May Also Like
-
Three Phases Power Testing System Transformer Coil Resistance TesterUS$ 1000 - 10000MOQ: 1 Set
-
Underground Pipe Cable Faults DetectorUS$ 1000 - 1000000MOQ: 1 Set
-
Transformer Oil Breakdown TesterUS$ 1000 - 10000MOQ: 1 Set
-
Insulated Gloves Gloves Acdc Hipot Test BarrelUS$ 1000 - 11000MOQ: 1 Set
-
Very Low Frequency High Voltage Tester (VLF-30/40/50)US$ 1000 - 50000MOQ: 1 Set
-
12 Channels Automatic High Voltage Switchgear Circuit Breaker AnalyzerUS$ 1000 - 10000MOQ: 1 Set
-
High Voltage Switchgear Circuit Breaker AnalyzerUS$ 1000 - 100000MOQ: 1 Set
-
HV/LV Switch Cabinet Test BenchUS$ 1000 - 10000MOQ: 1 Set
-
Customized Capacitance Impulse Current Generator Power Testing System Long LifeUS$ 4800 - 21000MOQ: 1 Set
-
Transformer Winding Deformation Analyzer (SFRA)US$ 1000 - 20000MOQ: 1 Set