A. areas of usage
1. Common reasons for using neutral groundingresistor
a. reducing single phase fault currents whichoccur in M.V. electrical networks to prevent damages on transformers andgenerators
b. reducing temporary over voltage occurred bybraking instantaneous fault current, providing long-life for switchgear
c. reducing step voltage to a harmless levelfor staff
Neutralgrounding resistors are used for resistance grounding of industrial powersystem. They are generally connected between ground and neutral of transfomers,generators and grounding transformers. Neutral grounding resistors are used inorder to limit maximum fault current to a value which will not damage theequipment in the power system, yet allow sufficient flow of fault current tooperate protective relays to clear the fault. Although it is possible to limitfault currents with high resistance neutral grounding resistors, phase toground short circuit currents can be extremely reduced. As a result of thisfact, protection devices may not sense the fault. Therefore, it is the mostcommon application to limit single phase fault currents with low resistanceneutral grounding resistors.
B. Features
Stainless-steelresistor elements
Currenttransformer included (EN60044-1)
Bolted resistorelement connections instead of welded connections in order to be able toassemble spare parts on site immediately.
MINGRUI resistorsare designed to absorb a large amount of energy without exceeding temperaturelimitations defined in IEEE32. Neutral Grounding Resistors MINGRUI manufacturecan be used for indoor and outdoor and the neutral point is connected with aporcelain bushing or with a high voltage cable from the bottom, top or side.The most common protection degree preferred for Neutral grounding resistors isIP23 as it allows the resistor elements to cool easier and they can be usedboth at sea shores and deserts because the resistor elements are completelystainless steel and does not affected by extreme conditions. Neutral groundingresistors are shipped with maintenance and installation guide, in which,recommended relay settings for each Neutral grounding resistor are stated aswell. MINGRUI provides complete technical assistance in order to meet yourspecifications or site conditions.
B.a TechnicalSpecifications
Operation voltage:up to 110kV line to line systems
Rated current (A):up to 2000
Ambienttemperature :<55
Resistance alloy:stainless steel
Protection degree:IP23(outdoor) and others
Standards: IEEE32,IEC60137, IEC60298, IEC60273, IEC60071, IEC60060
C. b
2mm hot dipgalvanized steel enclosure
Stainless steel oraluminum enclosures are available on demand
Typically, RAL7032paint for enclosure (other colors are available on demand)
Solid top coversloped to prevent water accumulation
Custom madelifting eye bolts for securing lifting
Front cover foreasy access to connection and inspection doors available on demand
Corrosionresistant stainless steel nameplate
B.c Options
Elevated supportstandard are provided for ground clearance and safety
Specially designedunits for hazardous and extreme locations
Stainless steel oraluminum enclosures on demand
Installation ofvoltage transformers
Installation ofprotection relays
Porcelain entrancebushings can be mounted on top or on the side of Neutral grounding resistor
Grounding transformerinstallation
Motorized ormanual single pole disconnector switches, load bank switches, surge arrestersand heaters in the Neutral Grounding Resistors
C. TESTS
C.a. Routine tests
Measurement ofinsulation resistance between enclosure and resistor
Withstand test ofdielectric strength at network frequency for one minute
Measurement oftotal DC resistance
Insulation test orresistor blocks
Galvanizationthickness test
Paint thicknesstest
C.b Type Test (ondemand)
Temperature risetest
Protection degreetest
Impulse voltagetest
Measurement of ACresistance
Seismic test
Send Inquiry to This Supplier
You May Also Like
-
S13-M·RL Three-dimensional Wound Core Oil Immersed TransformerNegotiableMOQ: 1 Piece
-
IP67 Plastic Portable Waterproof Electrical Power Distribution Boards BoxUS$ 10MOQ: 100 Pieces
-
Electrical Equipment Frequency ConverterUS$ 45 - 110MOQ: 5 Pieces
-
KYN28-12 High Voltage Skid-mounted Metal-enclosed SwitchgearUS$ 100 - 10,000MOQ: 1 Piece
-
Marine Electrical Main SwitchboardUS$ 1 - 500MOQ: 1 Unit
-
GPRS Outdoor Alarm Controller S250,Three-Phase Power Line Protection,NC/NO/EOL Dry Contact,Remote Relay OutputUS$ 1 - 10MOQ: 1 Set
-
Indoor Electric Meter Box Custom Made Supplier With 30 Years Manufacturing ExperienceUS$ 0.2 - 3.5MOQ: 500 Pieces
-
Cotton Digital Printing Processing Customized Group Cycling Clothes SuitNegotiableMOQ: 1 Piece
-
Distribution BoxNegotiableMOQ: 1 Piece
-
Small Gear Reducer MotorUS$ 8 - 10MOQ: 1 Piece