Home > Electrical & Electronics > Power Transmission & Transformer > Transformer > TKCJ Lightning Impulse Voltage Generator Complete Test Equipment

TKCJ Lightning Impulse Voltage Generator Complete Test Equipment

TKCJ Lightning Impulse Voltage Generator Complete Test Equipment photo-1
Negotiable MOQ: 1 Piece (Price negotiable depending on order volume and customization)
Key Specifications
Get Latest Price
Brand Name:
GDMK
Place of Origin:
China
Model Number:
TKCJ
Payment & Shipping
Payment Methods:
Port of Shipment:
China
Delivery Detail:
Delivery time depends on order quantity.
Brand Name GDMK
Place of Origin China
Model Number TKCJ
Product Introduction

Impulse voltage generator is mainly used for impulse voltage test of power equipment such as lightning impulse voltage full wave lightning impulse voltage truncation wave and operating impulse voltage wave to test insulation performance.Impulse voltage generator a power supply device that imitates impulse voltages such as lightning and operating overvoltages.It is mainly used in insulation shock withstand voltage and dielectric shock breakdown and discharge tests.

Scope of application: standard lightning shock lightning cut-off wave for transformers reactors mutual transformers and other high voltage electrical appliances high voltage thyristor valve SVC(HVDC) power cables all kinds of high voltage insulators bushing operation shock and all kinds of non-standard shock wave impulse voltage test required by users.Various test waveforms (standard and non-standard waveforms user-generated waveforms) can be generated by a single set of equipment.Field of application: lightning protection and lightning test for quality inspection measurement inspection and supervision organizations power equipment manufacturers railway communications aerospace and aerospace vehicles military research units universities and meteorological departments.

900kV/67.6 kJ Lightning Impulse Voltage Generator Complete Test Equipment for Transformer Reactor Cable
Product Parameters
Technical Parameters
Charging voltage Setting range 0 ~ 100kV
Scope of work 20 ~ 100kV
Setting deviation ≤ ±1%
Don't stability ≤ ±1%
Setting distinguish 0.1kV
Charging time Setting range 30~180s
Setting distinguish 1s
Alarm time delay 2s
Number of pressure Setting range 1~999
Protection setting Overcurrent protection

value

Can be set
Overvoltage protection

value

Can be set
Dynamic charge

protection

Can be set
Trigger pulse More than 15kV rising time less than 100ns polarity can be switched
Output impact stability More than 99%

Product Characteristics
  • Rated parameter value

    1. Nominal voltage: 900kV

    2. Rated voltage: 150kV

    3. Nominal energy: 67.6kJ

    4. Total impact capacitance: 0.167 microfarad (single pulse capacitor 2.0 microfarad / 75 kV 12 in total)

    5 the total number of levels: 6

    6. Standard waveform parameters:

    (1) Full lightning surge voltage

    Wave head time: 1.2us ± 30% uS wave tail time: 50us ± 20%

    Voltage utilization factor> 85% (greater than 90% at no load 300PF);

    (2) Standard cut-off: cut-off time 2-6uS zero-crossing coefficient ≤0.3% voltage utilization coefficient> 85%

    7. the minimum output voltage is greater than 10% of the nominal voltage

    8. Duration of use: Above 70% of rated voltage continuous operation can be performed after charging and discharging every 120 seconds and below 70% of rated voltage continuous operation can be performed after charging and discharging every 60 seconds.

Impulse Voltage Generator


Product Tags: highvoltage impulse generator high voltage 170 kv substation impulse test multi stage impulse voltage generator , Lightning Impulse Voltage Generator Complete Test Equipment

Send Inquiry to This Supplier

* Message
0/5000

Want the best price? Post an RFQ now!
Verified Business License
Business Type
Manufacturer
Year Established
2014
Main Markets
Southeast Asia

Recommended Categories

Explore top categories and find suppliers for your specific needs