Din Rail Multifunction Energy Meter For Array Cabinet AMC16MA
AMC16 series multi circuit monitoring device is a measuring device designed specifically for the power supply management of server in the data center.
Such device is small and exquisite in design, capable of centralized monitoring on various electric parameters and on-off states of dozens of
circuits,including incoming line circuit and outgoing line circuit, and it achieves the highly integration of monitoring circuits in volume.
Charactristics
Product Features
Monitoring Up to 12 Three-phase Circuits or 36 circuits Single phase
Measuring incoming main line 3 phase voltage
Incoming line: 2 channel 3 phase I,Kw,Kvar,cosφ,Kwh(current, active power, reactive power, power factor, active energy, reactive energy)
Outgoing line: 36 channel single phase (12 channel 3phase)I,Kw,Kvar,cosφ,Kwh,Kvarh(need to allocate AHK-0.66W 100A/20mA CTs
Inbuilt communication:1 channel RS485
1 DO, Power supply:AC 220V
-
Optional functions:
1.RS485/Modbus
2.DC48V power supply
Dimensions and Wirings
Wiring
Datasheet
| Input circuits | |
| Measuring incoming main line 3 phase voltage | |
| incoming line: 2 channel 3 phase I,Kw,Kvar,cosφ,Kwh(current, active power, reactive power, power factor, active energy, reactive energy) | |
| Rated input voltage: | AC220V |
| Measurement range: | AC 40~400V |
| Overload: | instantaneous voltage twice/30 seconds |
| rated input current: | inlet:5A outlet:20mA |
| measurement range: | inlet:5-10000A outlet:0.25-125A |
| Overload: | sustained voltage1.2times,instantaneous current 10times/5 seconds |
| Output circuits | |
| outgoing line: 36 channel single phase (12 channel 3phase) I,Kw,Kvar,cosφ,Kwh,Kvarh(need to allocate AHK-0.66W 100A/20mA CTs) | |
| Frequency | |
| 45-60HZ | |
| Auxiliary power supply | |
| AC80-270V or DC100V-350V/DC48V±20% | |
| Accuracy | |
| class 0.5(current,voltage ) ; class 1(power,energy) | |
| Relay output | |
| 5A/250VAC or 5A/30VDC | |
| Communication | |
| RS485 ModBus-RTU protocol | |
| Functions | |
| 1 DO, aux. power supply:AC 220V | |
| Optional functions | |
| 2*RS485 ModBus-RTU protocol | |
| DC 48V power supply | |
| Installation | |
| Din rail 35mm | |
Send Inquiry to This Supplier
You May Also Like
-
Smart Motor Protector ARD2F-25+90L Protection Relay With Leakage CurrentNegotiableMOQ: 1 Piece
-
Undervoltage Alarm Medium Voltage Application Protection Relay AM4-INegotiableMOQ: 1 Piece
-
AM5-T Overcurrent IDMT Protection Relay For Medium Voltage ApplicationNegotiableMOQ: 1 Piece
-
ARTM-P3-300 Wireless Temperature Measuring Equipment With RS485NegotiableMOQ: 1 Piece
-
Protection Device Relay With RS485 Communication Modbus-RTU AM2NegotiableMOQ: 1 Piece
-
ARTU-K32 Series Din Rail Mounting Remote Terminal UnitNegotiableMOQ: 1 Piece
-
ARD2-25 Motor Circuit Breaker Underload Protection RelayNegotiableMOQ: 1 Piece
-
AM4-I Undervoltage Alarm Medium Voltage Motor Protection RelayNegotiableMOQ: 1 Piece
-
Three Phase AM4-I Microcomputer Integrated Protection RelayNegotiableMOQ: 1 Piece
-
WHD20R-22 Two Channel Temperature And Humidity ControllerNegotiableMOQ: 1 Piece