SG (B) 10 Series Non-encapsulated H-class Dry-type Power Transformers,Dry Type Power Transformers,hermetically Sealed Transformers,dry Type Transformer
SG (B) 10 series Non-encapsulated H-class Dry-type Power Transformers
ZYDQ Dry Type Transformer Description
SG (B) 10 series of non-encapsulated H-class Dry type Power Transformers adopt the special process technology of German (MORA) dry-type transformers to ensure that the products fully meet the requirements such as fire prevention, waterproof ,environmental protection. It is the ideal product for distribution systems and widely used in the subway, shipbuilding, mining, chemical, power companies and personnel-intensive buildings as well as other special requirements of the occasion for safety.
Technical Parameter for 6kV, 10kV& 30kVA-2500kVA With Off Circuit Dry Type Transformer
Rated capacity(KVA) | Voltage Combination | Connection Group Symbol | No-load Loss(W) | Load Loss (W) | No-load Current (%) | Short-circuit Impedance(%) | |||||
High Voltage (KV) | Tapping ranges of High Voltage | Low Voltage(KV) | 130℃(B)(100℃) | 155℃(F)(120℃) | 180℃(H)(145℃) | ||||||
30 | 66.36.61010.511 | ±2X2.5%±5% | 0.4 | Dyn11Yyn0 | 190 | 670 | 710 | 760 | 2.0 | 4.0 | |
50 | 270 | 940 | 1000 | 1070 | 2.0 | ||||||
80 | 370 | 1290 | 1380 | 1480 | 1.5 | ||||||
100 | 400 | 1480 | 1570 | 1690 | 1.5 | ||||||
125 | 470 | 1740 | 1850 | 1980 | 1.3 | ||||||
160 | 540 | 2000 | 2130 | 2280 | 1.3 | ||||||
200 | ±2X2.5%±5% | 620 | 2370 | 2530 | 2710 | 1.1 | |||||
250 | 720 | 2590 | 2760 | 2960 | 1.1 | ||||||
315 | 880 | 3270 | 3470 | 3730 | 1.0 | ||||||
400 | 980 | 3750 | 3990 | 4280 | 1.0 | ||||||
500 | 1150 | 4590 | 4880 | 5230 | 1.0 | ||||||
630 | 1340 | 5530 | 5880 | 6290 | 0.85 | ||||||
630 | 1300 | 5610 | 5960 | 6400 | 0.85 | 6.0 | |||||
800 | 1520 | 6550 | 6960 | 7460 | 0.85 | ||||||
1000 | 1770 | 7650 | 8130 | 8760 | 0.85 | ||||||
1250 | 2090 | 9100 | 9690 | 10300 | 0.85 | ||||||
1600 | 2450 | 11000 | 11700 | 12500 | 0.85 | ||||||
2000 | 3050 | 13600 | 14400 | 15500 | 0.70 | ||||||
2500 | 3600 | 16100 | 17100 | 18400 | 0.70 | ||||||
1600 | 2450 | 1220 | 12900 | 13900 | 0.85 | 8.0 | |||||
2000 | 3050 | 15000 | 15900 | 17100 | 0.70 | ||||||
2500 | 3600 | 17700 | 18800 | 20200 | 0.70 | ||||||
Notes: The load losses listed in the table are the values of the reference temperature for different insulation systems in parentheses; The load losses under other insulation system temperatures that are not included in the table should be according to their respective reference temperatures, the corresponding calculation is based on the"- 155 ℃ (F)" insulation system temperature data.
Notes: The Dimension and weight will be changed according to the requirements. These two data in the table will be subject to the factory documents.
For more information about the Dry Type Transformer, click here
/
Send Inquiry to This Supplier
You May Also Like
-
Non-encapsulated H-class Dry-type Power TransformersNegotiableMOQ: 1 Piece
-
Resin-insulated Dry Type TransformerNegotiableMOQ: 1 Piece
-
Cast Resin Transformer,dry-type TransformerNegotiableMOQ: 1 Piece
-
Cast Resin Dry TransformerNegotiableMOQ: 1 Piece
-
Step up Dry TransformerNegotiableMOQ: 1 Piece
-
SG (B) 10 Series Non-encapsulated H-class Dry-type Power Transformers Product DescriptionNegotiableMOQ: 1 Piece
-
Prefabricated SubstationNegotiableMOQ: 1 Piece
-
XGN2 Type Modular High Voltage Switchgear,High Voltage Switchgear,High and Low Voltage SwitchgearsNegotiableMOQ: 1 Piece
-
KYN28A-12 (GZS1-12) Model Indoor AC Metal Clad Intermediate Switchgear,KYN28A-12 (GZS1-12) Indoor AC Metal Clad Intermediate Switchgear,Circuit Breaker Switchgear,High and Low Voltage Switchgears,Indoor AC SwitchgNegotiableMOQ: 1 Piece
-
GGD Low Voltage Fixed-mounted Switchgear,Fixed Mounted Switchgear,Low Voltage Switchgear,High and Low Voltage SwitchgearsNegotiableMOQ: 1 Piece