 All-in-one design relay tester with 6.4 inches LCD display
Binary Inputs Number: 8 pairs
Binary output Number :4 pairs

 With all in one design, able to test most of relays by manual or automation!

 Software Features:
1. Able to test most of Relays by manual or automation: Voltage relays, Current relays, Frequency relays, Power relays, Impedance relays, Harmonic relays, Distance relays etc;
2. With self housing-grounding-detecting function, the software interface can show whether the housing well grounding or not, effectively ensure the safety of testing.
Hardware Features:
1. All-in-one design relay tester with 6.4 inches LCD display;
2. 4 Phase AC Voltage Sauce and 3 phase AC current source can be output together, even the Range, Phase, Frequency can be set independently;
3. Max AC voltage can reach 300V each phase, Offer independent Aux. DC to tested devices, 0 ~ 300V/0.6A (Poleless and adjustable);
4. Offer different type of computer port: USB port, RJ45 port, VGA Video Port , USB / RJ45 ports convenient for data transfer, VGA Video Port can connect to projector and easy for study and training;
5. Super long life Rotary encoder + Functional keyboard.

 Technical Data of K68

Voltage generators

Setting 

Range

4-phase AC (L-N)

4 x 0 ... 300V 

2-phase AC (L-L)

2x 0 ...600 V

Power

4-phase AC (L-N)

4 x110VA,  at 0 ...300 V

2-phase AC (L-L)

2 x 220VA,  at 0 ...600 V

Accuracy

<0.07% reading + 0.03% range guaranteed at 0-300V

<0.04% reading + 0.01% range typical at 0-300V

Resolution

1mV

Current generators

Setting

Range

3-phase AC (L-N)

3 x 0 ... 35 A

1-phase AC (3L-N)

1 x 0 ...105 A 

Power

3-phase AC (L-N)

1x 450VA,  at 0 ... 35A 

1-phase AC (3L-N)

1 x 1000VA,  at 0 ...105A

Accuracy

<0.14% reading + 0.06% range guaranteed at 0-35A 

<0.05% reading + 0.02% range typical at 0-35A

Resolution

1mA

Generators,  general

Frequency

Range

0 ... 1000 Hz

Accuracy / drift

Error < 0.001Hz at 10 ... 65Hz,

Error < 0.01Hz at 65Hz...450Hz

Error < 0.02Hz at 450Hz...1000Hz

Resolution

0.001Hz

Phase

Range

- 360° ... +360°

Accuracy / drift

Error < 0.2 °

Resolution

0.1°

Time

Range

0 ... 999, 999.999s

Accuracy / drift

Error<1ms

DC generators

Voltage ranges

0 ... 300V/180VA 

Current ranges

0 ... 20A/300W

Accuracy

Error<0.1% reading + 0.1% range guaranteed at 0…300 V;

Error <0.1% reading + 0.1% range guaranteed at 0...20 A;

Send Inquiry to This Supplier

Message
0/5000
Want the best price? Post an RFQ now!
Business Type
Trading Company
Total Employees
101 - 200 People
Main Markets
North America, South America, Eastern Europe
Location
Rizhao, Shandong, China

Recommended Categories

Explore top categories and find suppliers for your specific needs