Home > Tools & Hardware > Hydraulic Parts > Hydraulic Cylinder > 24kv 50 / 60Hz Outdoor Vacuum 3 Phase Circuit Breaker Use for Power System 12kv Substation

24kv 50 / 60Hz Outdoor Vacuum 3 Phase Circuit Breaker Use for Power System 12kv Substation

24kv 50 / 60Hz Outdoor Vacuum 3 Phase Circuit Breaker Use for Power System 12kv Substation photo-1
Negotiable MOQ: 1 set (Price negotiable depending on order volume and customization)
Key Specifications
Get Latest Price
Brand Name:
Mingde Electrical
Place of Origin:
China
Model Number:
ZW32-24
Payment & Shipping
Payment Methods:
Port of Shipment:
China
Delivery Detail:
7 days
Brand Name Mingde Electrical
Place of Origin China
Model Number ZW32-24
Delivery Time:30 days
Certification:GB1984, IEC

24kv 50 / 60Hz Outdoor Vacuum 3 Phase Circuit Breaker use for Power System 12kv Substation
 

1. 3 Phase Circuit Breaker Summary

ZW32-24 type outdoor high voltage vacuum circuit breaker is three-phase AC,

50(60)Hz outdoor power distribution equipment with the rated voltage of 24kv,

Used to open and close the load current, over load current, and short circuit current in the electric power system. 

Also used to protect and control the circuit in substation, mining and industrial enterprises,  

and frequently used in the operation places such as rural power network. 

2. 3 Phase Circuit Breaker Using environmental condition 
A. The altitude above sea level does not over 2, 000 meters; 
B. Surrounding air temperature: -40 ℃ ~+40 ℃ ; 
C. The wind speed is not bigger than 34m/s; 
D. The air filthy should be with in Ⅲ degree
E. Installing places: Not flammable,  the explosion hazard,  chemistry corrode place; 
F. Does not have the regular fierce vibration

3. 3 Phase Circuit Breaker Technical parameter

Table 1  Circuit Breaker\'s Main Technical Data

Data

NO

Item

Unit

24kv

1

Rated voltage

kV

24

2

Rated frequency

Hz

50

3

Rated current

A

630/1250

4

Rated short circuit breaking current

kA

20/25

5

Rated peak withstand current

kA

50/63

6

Rated short time withstand current/ lasting time

kA/s

20/4 , 25/4

7

Rated short circuit closing current(peak)

kA

50/63

8

Rated operating sequence

O-0.3s-CO-180s-CO

9

Mechanical life

time

10000

10

Rated short circuit breaking current breaking times

0

11

1min power frequency withstand current

(wet)

kV

50/64

(dry)

kV

65/79

12

Lightning impulse withstand voltage(peak)

kV

125/145

13

Secondary circuit power frequency withstand voltage (1min)

V

2000

 Table2 Circuit Breaker\'s Main Mechanical Data

NO

Item

Send Inquiry to This Supplier

Message
0/5000

Want the best price? Post an RFQ now!
Business Type
Trading Company
Total Employees
101 - 200 People
Main Markets
North America, South America, Eastern Europe
Location
Liaocheng, Shandong, China

Recommended Categories

Explore top categories and find suppliers for your specific needs