Specifications
1. Eectrochemical CO sensor2.0~10VDC or 4~20mA output optional
3.RS485 interface
4. Smart structure and easy mounting
wholesale sensor carbon monoxide
CO Measurement | |
Gas detected | Carbon monoxide |
Sensing element | Battery operable electrochemical sensor |
Gas sample mode | Diffusion |
Warm up time | 1hour (first time) |
Response Time | Within 60 seconds |
Signal Update | 1s |
CO Measuring Range | 0~100ppm(default) 0~200ppm/0~500ppm selectable |
Accuracy | <±1ppm (at 20±5°C/ 50±20%RH) |
Stability | ±5% (over 900 days) |
Electrical |
|
Power Supply | 24VAC/VDC |
Consumption | 1.5 W |
Wiring connections | 5 terminal blocks (max.) |
Outputs | |
Linear analog output | 1x0~10VDC/4~20Ma selectable in order |
D/A resolution | 16 bit |
D/A conversion accuracy | 0.1ppm |
Modbus RS485 Communication interface | Modbus RS485 interface 9600/14400/19200(default), 28800 bps, 38400 bps (programmable selection), 15KV antistatic protection |
General Performance | |
Operation temperature | 0~60°C(32~140°F) |
Operation humidity | 5~99%RH, non condensing |
Storage conditions | 0~50°C(32~122°F) |
Net Weight | 190g |
Dimensions | 100mm×80mm×28mm |
Installation standard | 65mm×65mm or 2”×4” junking box |
Housing and IP class | PC/ABS fireproof plastic material, protection class: IP30 |
Compliance | EMC Directive 89/336/EEC |
1. Wall mounting, real time detect CO level with selectable three measuring ranges of 0~100ppm/ 0~200pm/ 0~500ppm.
2. Electrochemical sensor which offer several advantages over traditional electrochemical sensors with a long life, good long term stability, and high accuracy, especial environment friendly without risk of electrolyte leakage.
3.Simple calibration way Special design of easier replacement of the sensors
4.Full time CO level detection, even the slightest leak can be detected
5.One analog output with the linear relationship between CO gas concentration
6.Internal microprocessor control
7.Special built-in Self-Zero Correction algorithm.
8.RS-485 communication interface optional with 15KV antistatic protection, independent address setting
Send Inquiry to This Supplier
You May Also Like
-
Qualified HST CS Series Iron Ore Carbon Sulfur AnalyzerNegotiableMOQ: 1
-
Supply of Electric Carbon Products Carbon and Sulfur Analyzer, Mingrui mr - Cs995 Type, High - Frequency Infrared Carbon and Sulfur AnalyzerUS$ 6123.08 - 6584.62MOQ: 1 Unit
-
Honeywell EZtrend® GR Advanced Graphic Recorder AgentNegotiableMOQ: 1 Unit
-
Lora Wireless CO2 SensorUS$ 165 - 180MOQ: 1 Piece
-
TOC Offline AnalyzerNegotiableMOQ: 1 Set
-
DI1500 Water Detection Industrial Laboratory TOC Analyzer Price Total Organic Analyzer MeterUS$ 10,000 - 15,000MOQ: 1 Piece
-
Online Technique Support Toc Analyzer With Good PriceUS$ 1,000 - 15,000MOQ: 1 Piece
-
CONTACT BLOCK FOR TEMPERATURE AND OXYGEN SENSORS-4(CORE)OXY&2(CORE)TEMP. USED IN MEASURING OXYGEN&TEMPERATURE ACTIVITY OF MOLTEN METALS IN TYPES B,R,S&IN MARK VII MODELS.NegotiableMOQ: 1 Piece
-
Non Destructive Testing Glass Miniature X Ray Tube With Tungsten FilamentNegotiableMOQ: 1 Piece
-
20X 40X Jewelry Gem Stereo Optical Microscope Parallel Microscopes A22.1207US$ $1 - $1MOQ: 1 Piece