600V Cable XHHW-2 Type Aluminum Conductors
600V Cable XHHW-2 type aluminum conductors
Aluminum Alloy UL CSA Standard
Description
Voltage
600V or less
Construction
Sino-cables XHHW-2 type aluminum conductors are annealed AA-8000 series Aluminum Alloy, compact stranded. Insulation is an abrasion, moisture and high-heat resistant black cross-linked polyethylene. Conductor sizes AWG 2 and larger listed and marked sunlight resistant in black only.
Copper conductor is also available.
Standard
XHHW-2 conductors meet or exceed UL Standard 44 .Federal Specification A-A-59544, and requirements of the NEC Type XHHW-2 meets and exceeds all construction requirements of ICEA S-95-658(NEMA WC 70)-Non shielded 0-2kv Cables, with testing frequencies based on UL requirements.
Features
1.-40℃----90℃
2.High-Heat and Moisture and Sunlight Resistant.
3.VW-1 or higher required by UL.
Applications
1.XHHW-2 conductors are primarily used in conduit or recognized raceways for services, feeders, and branch circuit wiring as specified in the National Electric Code(NEC).
2.May also be used in wet or dry locations at temperatures not to exceed 90℃.
3.Voltage rating for RW90 cable is 600V.
Package
steel & wooden reel, wooden reel, steel reel, in coils on wooden tray, or other requirements by customers.
W E I G H T S. M E A S U R E M E N T S | ||||||
CONDUCTOR SIZE |
INSULATION |
NOMINAL O.D. |
ALLOWABLE |
APPROXIMATE |
||
60℃ |
75℃ |
90℃ |
||||
8 |
45 |
228 |
30 |
40 |
45 |
31 |
6 |
45 |
263 |
40 |
50 |
60 |
43 |
4 |
45 |
307 |
55 |
65 |
75 |
67 |
2 |
45 |
362 |
75 |
90 |
100 |
87 |
1 |
55 |
413 |
85 |
100 |
115 |
109 |
1/0 |
55 |
450 |
100 |
120 |
135 |
133 |
2/0 |
55 |
490 |
115 |
135 |
150 |
162 |
3/0 |
55 |
537 |
130 |
155 |
175 |
201 |
4/0 |
55 |
589 |
150 |
180 |
205 |
246 |
250 |
65 |
654 |
170 |
205 |
230 |
297 |
300 |
65 |
704 |
190 |
230 |
255 |
352 |
350 |
65 |
750 |
210 |
250 |
280 |
402 |
400 |
65 |
793 |
225 |
270 |
305 |
454 |
500 |
65 |
870 |
260 |
310 |
350 |
555 |
600 |
80 |
980 |
285 |
340 |
385 |
680 |
700 |
80 |
1041 |
310 |
375 |
420 |
783 |
750 |
80 |
1072 |
320 |
385 |
435 |
832 |
1000 |
80 |
1224 |
375 |
445 |
500 |
1091 |
|
* Ampacities for not more than three conductors in raceway, based on ambient temperature of 30°C per Table 310-16 of the 2005 National Electrical Code (NFPA 70-1990). 90°C - XHHW wet or dry locations for ampacity adjustment purposes using NEC section 310.1. * All values are nominal and subject to correction. | ||||||
Send Inquiry to This Supplier
You May Also Like
-
Mining CableUS$ 1 - 100MOQ: 1 Kilometer
-
Overhead Cable (GB)/ Copper, or Alloy Conductor Insulated With PVC, XLPE or PE UndergroundUS$ 1 - 100MOQ: 1 Kilometer
-
450/750V Factory Price Rubber Cable IEC StandardUS$ 1 - 100MOQ: 1 Kilometer
-
Mineral-insulated Metal Sheath Flexible Fire-proof CableUS$ 1 - 100MOQ: 1 Kilometer
-
RWU90 1KV(solar)US$ 1 - 100MOQ: 1 Kilometer
-
Rhh/Rhw-2 - Aluminum Conductor UL StandardUS$ 1 - 100MOQ: 1 Kilometer
-
2kV DLO Cable for Wind TurbineUS$ 1 - 100MOQ: 1 Kilometer
-
Xhhw-2 Aluminum CableUS$ 1 - 100MOQ: 1 Kilometer
-
RHH or RHW-2 or USE-2 Aluminum Conductors Are AA-8000 Series Aluminum AlloyUS$ 1 - 100MOQ: 1 Kilometer
-
Rubber Cable (IEC)US$ 1 - 100MOQ: 1 Kilometer