Specifications
1.Mechanical switch contact2.Versatile fields of application
3.Small size
4.Easy to connect
lc013 for regulating and monitoring fan controller
The airflow monitor (NC/NO) is designed to indicate the loss of air movement of a fan or filter fan.
The contact detects the loss of air movement caused by fan failure or blocked filter media regardless of direction of air.
Its simple mechanical operation makes it a viable alternative to electronic monitoring systems.
Technical Data
| Contact type | reed / magnet contact |
| Normally closed (NC) | switch contact open when air is flowing |
| Normally open (NO) | switch contact closed when air is flowing |
| Max. switching voltage | NC: 240VDC (UL), 240V AC/DC (VDE) / NO: 60VDC |
| Max. switching current | NC: DC 500mA / NO: DC 170mA |
| Max. switching capacity | 10W (resistive load) |
| Switching threshold of airflow velocity | > 2.5m/s (hysteresis: > 1m/s) |
| Max. airflow velocity | 50m/s |
| Contact resistance | < 370mOhm (with wire) |
| Max. air humidity | 70% RH (not precipitating) |
| Service life | > 100 000 cycles |
| Connection | 2 x single strand AWG 28, length 500mm, tip of stranded wire 5mm stripped and tinned (NC: black, NO: blue) |
| Mounting | alternatively integrated in protective grille (see table), mounting clamp or mounting clip |
| Casing | plastic according to UL94-HB, black |
| Fitting position | bidirectional tab perpendicular to airflow |
| Operating/Storage temperature | -20 to +50°C (-4 to +122°F) / -20 to +80°C (-4 to +176°F) |
| Protection type | IP20 |
| Approvals | VDE + UL File No. E250507 |
| Note | The product of switching voltage and switching current must not exceed 10W. The max. voltage and max. current must not be exceeded, not even short-term (voltage/current peaks). The resulting voltage and current peaks of inductive or capacitive loads must be restricted by a contact protection circuit. |
| Description | Art. No. (NC) | Art. No. (NO) | Weight (approx.) |
| Airflow monitor with mounting clamp and mounting clip LC 013 | 01300.0-00 | 01300.1-00 | 5g |
| Airflow integrated in protective grille (plastic) LCF 013 | 01301.0-00 | 01301.1-00 | 20g |
| Airflow integrated in protective grille (plastic) LCF 013 | 01302.0-00 | 01302.1-00 | 20g |
| Airflow integrated in protective grille (plastic) LCF 013 | 01303.0-00 | 01303.1-00 | 30g |
Technical Drawing
Example of connection
Airflow monitor Display
About SAIP
Send Inquiry to This Supplier
You May Also Like
-
Honeywell EC7890B1028 Burner Control EC7890 B 1028 Honeywel EC7890B1028/UNegotiableMOQ: 1 Piece
-
Raythink PC4 All-in-One PTZ Camera: Forest Fire Monitoring & Perimeter SecurityNegotiableMOQ: 50 Pieces
-
Water Transfer Mould Temperature MachineNegotiableMOQ: 2 Sets
-
16A Electric Heating Touch Screen Thermostat With WIFI for Floor Heating SystemUS$ 20 - 35MOQ: 10 Pieces
-
Gas Cooker Thermocouple Universal Gas ThermocoupleNegotiableMOQ: 1
-
Industrial Object Thermometer/Industrial ThermometerUS$ 23.5 - 23.5MOQ: 10 Pieces
-
Liyi Plastic HDT Point Tester Vicat Softening TemperatureUS$ 2,580 - 5,680MOQ: 1 Set
-
RC-5 USB Waterproof Temperature RecorderUS$ 10.6 - 19.2MOQ: 1 Piece
-
Easy to Use Black Body Radiation Source With Good GuaranteeUS$ 1,800 - 1,800MOQ: 1 Set
-
HONEYWELL 2MLR-CPUH/F MASTERLOGIC 200 PROGRAMMABLE LOGIC CONTROLLER 2MLR-CPUH HoneywelNegotiableMOQ: 1 Piece