Home > Electrical & Electronics > Optical Fiber, Cable & Wire > Electric Wire & Cable > 64/110kv,76/132kv Premolded Cold-shrinkable Outdoor Cable Termination

64/110kv,76/132kv Premolded Cold-shrinkable Outdoor Cable Termination

64/110kv,76/132kv Premolded Cold-shrinkable Outdoor Cable Termination photo-1
64/110kv,76/132kv Premolded Cold-shrinkable Outdoor Cable Termination photo-2
64/110kv,76/132kv Premolded Cold-shrinkable Outdoor Cable Termination photo-3
64/110kv,76/132kv Premolded Cold-shrinkable Outdoor Cable Termination photo-4
64/110kv,76/132kv Premolded Cold-shrinkable Outdoor Cable Termination photo-5
64/110kv,76/132kv Premolded Cold-shrinkable Outdoor Cable Termination photo-6
US$ 10 - 400 MOQ: 1 Set
Key Specifications
Get Latest Price
Place of Origin:
Shandong, China
Brand Name:
ASUNT
Model Number:
QX-NL
Payment & Shipping
Payment Methods:
Port of Shipment:
qingdao port
Delivery Detail:
Delivery time depends on order quantity.
Place of Origin Shandong, China
Brand Name ASUNT
Model Number QX-NL
Conductor Material Copper
Insulation Material Rubber
Jacket Rubber
Number of Conductors 3
Application 1KV

Specifications

outdoor cable termination
1.perfect protection and insulation
2.anti-tracking
3. easy and fast installation

 

Premolded cold-shrinkable outdoor cable termination

Description:

 

Cold shrink tubing is a fast and easy way to weatherproof a connection.  Simply position the pre-expanded tubing over the connection that you are protecting and

pull the rip cord. The tubing compresses to form a weatherproof seal.

 

 

Type and Specification:

 

  

Product type

Suitable cable section  mm2

Product type

Suitable cable section  mm2

10KV single core indoor use

20-50

35KV single core indoor use

50-95

70-150

120-185

185-400

240-400

10KV single core outdoor use

20-50

35KV single core outdoor use

50-95

70-150

120-185

185-400

240-400

10KV three core indoor use

20-50

10KV three core indoor use

50-95

70-150

120-185

185-400

240-400

10KV three core outdoor use

20-50

10KV three core outdoor use

50-95

70-150

120-185

185-400

240-400

 

 

 

Tech Data:

 

 

 

No. Test Project Standard Requirements Conclusion
1 Power Frequency Voltage 39KV 5min No Flashover and No Breakdown pass
2 Partial Discharge Under 15KV, Discharge volume10pc pass
3 Impulse Voltage Test Under 95KV, ±10times No flashover and No Breakdown
4 Constant Voltage load Cycle(in air) The conductor applied voltage 23KV, and heated to (95-100°C). In which the temperature stability 2h,cooling 3h, a total of 3cycles. Not flashover and assessed by the following test result
5 Constant load Cycle test The conductor applied voltage 23KV, and heated to (95-100°C). In which the temperature stability 2h,cooling 3h, a total of 6cycles. Not flashover and assessed by the following test result
6 Thermal Stability Test Under 23KA, Short circuit 2 times, No visible damage. pass
7 Dynamic Stability Test Under 81KA, Short circuit 1 time, No visible damage pass
8 AC Withstand Voltage 23KV, 15min No flashover and No Breakdown
9 Tide Temperature Test 11KV, 300h pass
10 Salt Spray Test 11KV, 1000h pass

 

 

 

64/110kv,76/132kv Premolded cold-shrinkable outdoor cable termination

64/110kv,76/132kv Premolded cold-shrinkable outdoor cable termination64/110kv,76/132kv Premolded cold-shrinkable outdoor cable termination64/110kv,76/132kv Premolded cold-shrinkable outdoor cable termination64/110kv,76/132kv Premolded cold-shrinkable outdoor cable termination

 

ASUNT group 

contact Ms Alice 

skype: asunalice

mobile:86+18300290219

 

Send Inquiry to This Supplier

Message
0/5000

Want the best price? Post an RFQ now!
Business Type
Manufacturer, Trading Company
Year Established
2010
Factory Size
Below 1,000 square meters
Total Employees
51 - 100 People