Home > Electrical & Electronics > Power Supply & Distribution > Power Distribution Cabinet & Box > 8.7/15kV Cold Outdoor Termination Structure Drawing

8.7/15kV Cold Outdoor Termination Structure Drawing

8.7/15kV Cold Outdoor Termination Structure Drawing photo-1
US$ 24 - 169 MOQ: 10 Sets
Key Specifications
Get Latest Price
Place of Origin:
Jiangsu, China
Brand Name:
C
Model Number:
WLS-10
Payment & Shipping
Payment Methods:
Port of Shipment:
Shanghai
Delivery Detail:
Delivery time depends on order quantity.
Place of Origin Jiangsu, China
Brand Name C
Model Number WLS-10

 

Rated voltage UO/U (Um) KV

6/10(12.5)

8.7/15(17.5)

26/35(40.5)

Railway Uo=27.5

Test result

5min frequency voltage test

no flashover, without breakdown under 4.5Uo

no flashover, without breakdown

1min frequency voltage under rain test

 

no flashover, without breakdown under 4Uo

no flashover, without breakdown

Partial discharge at room temperature test

discharge volume under 1.73Uo ≤10PC

≤1.6pC

Constant voltage load cycle in the air test

heated 2.5Uo and conductor to a temperature to 95-100°C three times, no flashover, without breakdown

no flashover, without breakdown

Partial discharge at high temperature test

heated cable conductor to 95-100C,discharge volume under 1.73Uo ≤10PC

≤1.6pC

Partial discharge at room temperature test

discharge volume under 1.73Uo ≤10PC

≤1.6pC

Impulse voltage at high temperature test

75 kV 

95 kV

200 kV

250 kV

no flashover, without breakdown

heated cable conductor to 95-100°C,both positive and negative polarity 10 times, no flashover, without breakdown

Constant voltage load cycle test

heated 2.5Uo and conductor to a temperature to 95-100°C sixty times, no flashover, without breakdown

no flashover, without breakdown

Partial discharge at high temperature test

heated cable conductor to 95-100°C,,discharge volume under 1.73Uo ≤10PC

≤1.6pC

Partial discharge at room temperature test

discharge volume under 1.73Uo ≤10PC

≤1.6pC

Impulse voltage test

75 kV 

95 kV

200 kV

250 kV

no flashover, without breakdown

both positive and negative polarity 10 times, no flashover, without breakdown

15min frequency voltage test

no flashover, without breakdown under 2.5Uo

no flashover, without breakdown

Outdoor terminal salt spray test

1.25 Uo,1000h,no flashover, without breakdown, no significant electrical corrosion and mechanical damage

no flashover, without breakdown

Indoor terminal wet test

1.25 Uo,300h,no flashover, without breakdown, no significant electrical corrosion and mechanical damage

no flashover, without breakdown

 

 

 

 

 

 

 

 

 

 

 

 

 