Home > Electrical & Electronics > Breaker & Protector > Fuse > HV HRC Fuse Diameter=76mm

HV HRC Fuse Diameter=76mm

HV HRC Fuse Diameter=76mm photo-1
HV HRC Fuse Diameter=76mm photo-2
HV HRC Fuse Diameter=76mm photo-3
HV HRC Fuse Diameter=76mm photo-4
US$ 6.9 - 27.5 MOQ: 30 Pieces
Key Specifications
Get Latest Price
Place of Origin:
Zhejiang, China
Brand Name:
SR
Model Number:
XRNT1( type S )
Payment & Shipping
Payment Methods:
Port of Shipment:
Shanghai or Ningbo
Delivery Detail:
Delivery time depends on order quantity.
Place of Origin Zhejiang, China
Brand Name SR
Model Number XRNT1( type S )
Usage High Voltage
Breaking Capacity High
Safety Standards IEC

Applications

H.V current-limiting fuses type S is mainly used in AC50Hz,rated voltage 3.6~40.5KV,rated current up to 200A circuit for protection transformers and power equipments from overload and short-circuit.It can also be used with load switch,vacuum contact.
It conforms to IEC282-1,GB15166.2 and DIN standard.

 

Design Features

S type H.V HRC current-limiting fuses is insert installation.The striker parallers to the fuse element made from pure silver.They are sealed in the fuse tube filled with chemically treated high-purity quartz  sand.The fuse tube is made from heat resistance,high duty ceramic or expoxy glass.

When fault circuit happens,the fuse link melts,the high-resistant metal wire paralleling to fuse links melts immediately at the appearance of the arc,and the striker jumps out to push the chained equipment contact, signaling the melting automatically cuttig the circuit.

The striker has spring type striker jumps out to push ethe chained equipment contact,signaling the melting automatically cutting the circuit.The striker has spring type striker use high pressure caused by the lighting powder to push the striker.

S type H.V.HRC current-limiting fuses has many merits as high current-limiting ablilty,high breaking capacity,quick and punctual in action,reliable in performance.

 

DIN HRC "S" type high voltage fuse for transformer protection:

1. According to bussmann DIN "S" type high performance back-up fuse

. Comply with IEC282-1, DIN, BS

3. This fuse is intended to protect distribution networks and transformer, for indoor as well as outdoor use.

4. Any other specifications can be designed specially.

 

 HV HRC fuse diameter=76mmHV HRC fuse diameter=76mm

 

Basic Data

 

model

Rated 

voltage 

(KV)

rated current                            

of the fuse links                     

(A)

Rated 

breaking 

current                        

(KA)

dimensions                  

(mm)

Foreign Department
SDO.J XRNT1 3.6 see figure 1 6.3/10/16/20/25/31.5/40 50 51 192
SDL.J XRNT1 7.2 see figure 1 6.3/10/16/20/25/31.5/40/50/63 50 51 292
SFL.J XRNT1 7.2 see figure 1 80/100/125/160 50 76 292
SDL.J XRNT1 12 see figure 1 6.3/10/16/20/25/31.5/40 50 51 292
SFL.J XRNT1 12 see figure 1 50/63/71/80/100 50 76 292
SKL.J XRNT1 12 see figure 1 125 50 76 292
SXL.J XRNT1 12 see figure 1 160/200 50 88 292
SDM.J XRNT1 24 see figure 2 6.3/10/16/20/25/31.5/40 40 51 442
SFM.J XRNT1 24 see figure 1 50/63/71/80/100 40 76 442
SKM.J XRNT1 24 see figure 1 125 40 76 442
SXM.J XRNT1 24 see figure 1 160 40 88 442
SDQ.J XRNT1 40.5 see figure 3 3.15/6.3/10/16/20/25 31.5 51 537
SFQ.J XRNT1 40.5 see figure 3 31.5/40 31.5 76 537
SXQ.J XRNT1 40.5 see figure 3 63 31.5 88 537

 

Note:under stipulated comdition,min.breaking current of fuses could be as high as 2.5~3 times than rated current.

Striker: N-without striker; A-powder type; D-spring type.

  

 

Transformer 

capacity

 (KVA)

                             ransformer primary voltage
7.2 (KV)  10(KV) 20(KV) 30(KV)

Fuse model/               

rated current(A)

Fuse model/                   

 rated current(A)

Fuse model/                      

rated current(A)

Fuse model/              

 rated current(A)

50 SDL.J-7.2KV/8A SDL.J-12KV/6.3A SDM.J-24KV/3.15A SDQ.J-40.5KV/3.15A
100 SDL.J-7.2KV/16A SDL.J-12KV/10A SDM.J-24KV/6.3A SDQ.J-40.5KV/6.3A
125 SDL.J-7.2KV/20A SDL.J-12KV/12A SDM.J-24KV/6.3A SDQ.J-40.5KV/6.3A
160 SDL.J-7.2KV/25A SDL.J-12KV/16A SDM.J-24KV/8A SDQ.J-40.5KV/6.3A
200 SDL.J-7.2KV/31.5A SDL.J-12KV/20A SDM.J-24KV/10A SDQ.J-40.5KV/8A
250 SDL.J-7.2KV/40A SDL.J-12KV/25A SDM.J-24KV/12A SDQ.J-40.5KV/10A
300/315 SDL.J-7.2KV/50A SDL.J-12KV/31.5A SDM.J-24KV/16A SDQ.J-40.5KV/10A
400 SDL.J-7.2KV/63A SDL.J-12KV/40A SDM.J-24KV/20A SDQ.J-40.5KV/16A
500 SDL.J-7.2KV/80A SDL.J-12KV/50A SDM.J-24KV/25A SDQ.J-40.5KV/16A
630 SDL.J-7.2KV/100A SDL.J-12KV/63A SDM.J-24KV/31.5A SDQ.J-40.5KV/20A
750/800 SDL.J-7.2KV/125A SDL.J-12KV/80A SDM.J-24KV/40A SDQ.J-40.5KV/25A
1000 SDL.J-7.2KV/160A SDL.J-12KV/100A SDM.J-24KV/50A SDQ.J-40.5KV/31.5A
1250   SDL.J-12KV/125A SDM.J-24KV/63A SDQ.J-40.5KV/40A
1600   SDL.J-12KV/160A SDM.J-24KV/80A SDQ.J-40.5KV/50A
2000   SDL.J-12KV/200A SDM.J-24KV/100A SDQ.J-40.5KV/63A

 

 HV HRC fuse diameter=76mmHV HRC fuse diameter=76mm

 

 HV HRC fuse diameter=76mm


 

 

 

 

 

 