8zone Fire Alarm Control Panel

8zone Fire Alarm Control Panel photo-1
Negotiable MOQ: 1 set (Price negotiable depending on order volume and customization)
Key Specifications
Get Latest Price
Place of Origin:
Ukraine
Brand Name:
ARTON
Model Number:
ARTON-08F
Payment & Shipping
Payment Methods:
Port of Shipment:
China
Delivery Detail:
Delivery time depends on order quantity.
Place of Origin Ukraine
Brand Name ARTON
Model Number ARTON-08F

ARTON-08F

fire alarm control panel

 

EN54-2:2003

EN54-4:2003

Designed for centralized and stand-alone protection of various applications against fires and unauthorized intrusion by controlling statuses of up to 8 alarm loops.

 

FEATURES:

  • each of panel’s loop can be adjusted as: fire alarm loop with verification, without verification, waiting for two detectors’ activation, intruder without delays, intruder with delays  to input/output, intruder “hallway” type, intruder 24-hour monitoring.
  • The panel defines and displays the following statuses of a fire alarm loop: “Standby”, “Attention” (verification of alarm loop or activation of the first detector),  “Fire”, “Fault – SC”, “Fault – OC”, “AL disabled”.
  • The panel defines and displays the following statuses of an intruder alarm loop: armed, disarmed, “Attention” – delay to input/output, “Alarm”, activation of detector in disarmed zone.
  • Passive and active detectors can be interconnected to one AL, combined alarm loops can be constructed using 2- and 4- wire wiring diagrams.
  • The possibility of changing the threshold deviation current in AL to determine detectors’ activation (separately for passive and active detectors).
  • The possibility of construction of combined ALs with verification or expectation for 2 detectors activation and priority of manual call point‘s activation.
  • 2 programmable powerful outputs “Out1” and “Out2” (300 mA current load) with programmable operation logics and operation options as power output of 4-wire AL, output to detector or incommutable power output of auxiliary devices (+12V).
  • 4 programmable low-current outputs “K1”..”K4” (40 mA current load) that form output signals  on combination AND/OR of “Fire” and “Fault” status in various ALs.
  • The panel defines the following types of faults and statuses: short-circuit or open-circuit of AL, short-circuit of outputs, load break of outputs “Light”, “Sound”, “Fire”, “Fault”, no voltages powering outputs and AL, no 220 V power, fault of storage battery etc.
  • 8 programmable authorized user access codes and 1 engineer access code.
  • Possibility to assign rights for each user to control the certain AL.
  • Possibility to change threshold current of determination of detectors’ activation in AL (separately for passive and active detectors).
  • Module architecture optimizing the panel’s configuration. Auxiliary modules: BR4-4 blocking relays, BSKT-1 auto-dialing module through commutable telephone lines, BSKM-1 GSM-communicator, BSPC-1 computer coupler.
  • Review of current configuration and programming (configurating) of the panel made from inbuilt keypad or from a computer using BSPC-1.

 

TECHNICAL SPECIFICATIONS:

Mains supply voltage      

220 (+22-33) V  50±1 Hz

Battery size 

12±15%V 7Ahr

Max AC power

30 W

Max storage battery current consumption

1,2 A 

Standby AC power

< 17 W

Standby operation time of the panel powered by the fully charged storage battery at mains outage

≤24 hours, including ≥3 hours  in the “Fire” mode

Max number of circuits

8

N.O. contact supply voltage

15 (±1) V

Output voltage at rated load

12 (±2) V

Total line resistance (not considering EOL resistor)

≤220 Ohm

Resistance of leakage between lines (EOL resistor disabled) and between each AL line and panel’s enclosure

≥50 kOhm

AL current interpreted by the panel as Open-circuit

from 0 to 3 mA

AL current interpreted by the panel as Short-circuit

>25 mA

Short-circuit limit current in AL

(28±2,8) mA

the AL status change duration the panel responses to

the AL status change duration the panel doesn’t issue the message about

≥100 ms

 

≥50 ms

Max number of active detectors (SPD-3, SPD-3.5, SPD-3.10, SPT-2B, SPT-3B etc.) interconnected to one loop.

 Max total current should not exceed 3 mA.

32

Auto-reset time (disablement time) of AL at verification (set by a user)

5-40 s

Time of expectation for repeated  triggering after AL resetting,

the panel goes to the “Fire” mode on detecting it

20-180 s

Specifications of connectable bells, sounders and beacons

12 (±2) V,  300 mA

Max current load of “Out1” and “Out2” outputs

300 mA

Max current load of “Fire”, “Alarm”, “Fault”, “K1”-“K4”

40 mA

Meantime-between-failures

30000 hours

Average lifetime

10 years min

Dimensions

300x240x100 mm

Weight (storage battery excluding)

3,5 kg 