Round and Counter Water Cooling Tower
Specifications
Cooling tower :1,Made of FRP composite material
2,PVC&PP two materials
3.The rotating components are imported bearings
I. Cooling tower Working condition :
Water inlet temperature:37°C
Water outlet temperature:32°C
Wet bulb temperature:28°C
Dry bulb tem peranure:31.8°C
Atmospheric pressure:9.94×10000Pa
Material: glass fiber reinforced plastic (GFRP)
II. Environmental choice
1, Should avoid installed in waterproof channel, easy to reflect the walls of volume, must be packed in roof or air circulation place.
2, With two or more cooling tower and, attention shall be paid to minus its spacing.
3, Should not be installed in all outer wall or tight place, and should pay attention to minus its exterior wall spacing.
4, Should avoid to install a soot and dust more places, the top jams film.
5, Should be far away from the kitchen and boiler room wait until a hot place.
III.Technology parameter of Cooling tower :
|
Model
|
Water flow |
Fan diameter |
Theoretical air |
Motor power |
Tower height |
Tower diameter |
Weight |
(m3/h) |
(mm) |
(m3/h) |
(kw) |
(mm) |
(mm) |
(kg) |
|
XTM-8 |
8 |
584 |
4500 |
0.18 |
1560 |
930 |
64 |
XTM-10 |
10 |
584 |
5700 |
0.18 |
1670 |
1000 |
85 |
XTM-12 |
12 |
760 |
6800 |
0.37 |
1700 |
1100 |
94 |
XTM-15 |
15 |
760 |
9100 |
0.37 |
1780 |
1250 |
124 |
XTM-20 |
20 |
760 |
11300 |
0.37 |
1780 |
1400 |
158 |
XTM-25 |
25 |
760 |
15000 |
0.55 |
1780 |
1400 |
174 |
XTM-30 |
30 |
884 |
17000 |
0.75 |
1960 |
1620 |
185 |
XTM-40 |
40 |
884 |
21000 |
0.75 |
2010 |
1740 |
192 |
XTM-50 |
50 |
884 |
23000 |
1.1 |
2010 |
1840 |
215 |
XTM-60 |
60 |
1190 |
28000 |
1.1 |
2400 |
2200 |
412 |
XTM-70 |
70 |
1190 |
33000 |
1.5 |
2530 |
2200 |
476 |
XTM-80 |
80 |
1470 |
45000 |
2.2 |
2680 |
2500 |
680 |
XTM-90 |
90 |
1470 |
48000 |
2.2 |
2710 |
2500 |
730 |
XTM-100 |
100 |
1470 |
50000 |
2.2 |
2820 |
2900 |
776 |
XTM-125 |
125 |
1800 |
57000 |
4 |
3130 |
3300 |
954 |
XTM-150 |
150 |
1800 |
70000 |
4 |
3350 |
3300 |
1062 |
XTM-175 |
175 |
1800 |
85000 |
4 |
3670 |
3600 |
1468 |
XTM-200 |
200 |
1800 |
99000 |
4 |
3900 |
4000 |
1797 |
XTM-225 |
225 |
2400 |
113000 |
5.5 |
4165 |
4500 |
1987 |
XTM-250 |
250 |
2400 |
142000 |
5.5 |
4290 |
4500 |
2370 |
XTM-300 |
300 |
3000 |
171000 |
7.5 |
4435 |
4900 |
2495 |
XTM-350 |
350 |
3000 |
210000 |
11 |
4735 |
5300 |
2702 |
XTM-400 |
400 |
3400 |
228000 |
11 |
4820 |
6100 |
3592 |
XTM-450 |
450 |
3400 |
285000 |
15 |
4820 |
6100 |
3741 |
XTM-500 |
500 |
3700 |
342000 |
15 |
5145 |
6800 |
4276 |
XTM-600 |
600 |
3700 |
400000 |
18.5 |
5145 |
6800 |
4457 |
XTM-700 |
700 |
4200 |
456000 |
22 |
5732 |
8000 |
6167 |
XTM-800 |
800 |
4200 |
570000 |
22 |
5732 |
8000 |
6445 |
IV. Operation inspection
1 , Keep the water tower in clean, regular water treatment.
2, Operation about 60 h, it should check belt tension ensure normal.
3, Gearbox oil level and running 150 h must be replaced after oil.
Send Inquiry to This Supplier
You May Also Like
-
10T Round and Counter Cooling TowerUS$ 275 - 300MOQ: 1 Set
-
15T Round and Counter Cooling TowerUS$ 360 - 395MOQ: 1 Set
-
20T Round and Counter Cooling TowerUS$ 150 - 5,000MOQ: 1 Set
-
25T Round and Counter Cooling TowerUS$ 475 - 530MOQ: 1 Set
-
30T Round and Counter Cooling TowerUS$ 710 - 790MOQ: 1 Set
-
Commercial Round Counter Current Cooling TowerUS$ 135 - 6,000MOQ: 1 Set
-
XTM Series Round Counter Current Cooling TowerUS$ 135 - 6,000MOQ: 1 Set
-
XTH Series Round Counter Current Cooling TowerUS$ 135 - 6,000MOQ: 1 Set
-
China Direct Manufacture Hot Sale Round Cooling Tower for SaleUS$ 165 - 6,000MOQ: 1 Set
-
Round Counter Current Cooling Tower Made in ChinaUS$ 135 - 6,000MOQ: 1 Set