1. Features CVT self-excitation method testing, simultaneously measuring the capacitance and tanδ of C1 and C2 with a single
connection.
2. Features reverse connection low-voltage shielding and high-voltage shielding functions. With the CVT bus grounded, it can perform
10kV reverse connection dielectric loss measurement on C11 without disconnection.
3. Features external voltage and external CN measurement functions.
4. Features CVT turns ratio measurement function, meeting the turns ratio measurement needs of CVT devices ranging from 35-500kV.
5. Features multi-channel simultaneous measurement function, capable of simultaneously testing the dielectric loss values of four test
objects.
6. Features insulation resistance testing function, capable of testing polarization index, absorption ratio, and insulation resistance.
7. Features automatic LCR measurement function, capable of measuring inductance, capacitance, and resistance.
8. Employs frequency conversion technology to eliminate 50Hz power frequency interference in the field, ensuring reliable data even
in environments with strong electromagnetic interference.
9. Overcurrent protection function, protecting the instrument from damage in the event of a short circuit or breakdown of the test object.
10. Includes standard capacitors and a high-voltage power supply for easy on-site testing and reduced wiring.
11. The instrument features a large LCD screen, is easy to operate, and provides prompts throughout the testing process.
12. The instrument's interface includes corresponding wiring diagrams, greatly simplifying wiring for the operator.
1. Operating Conditions: -15℃-40℃, RH<80%
2. Anti-interference Principle: Frequency Conversion Method
3. Power Supply: AC 220V±10%, Generator Allowed
4. High Voltage Output: 0.5KV - 12KV, in 0.1kV increments
5. Accuracy: 2%
6. Maximum Current: 200mA
7. Capacity: 2000VA
8. Self-Excited Power Supply: AC 0V-50V 15A
9. Single Frequency: 45.0Hz-65.0Hz, Adjustable
10. Dual Frequency: 45.0Hz 55.0Hz 47.5Hz 52.5Hz
55.0Hz 65.0Hz 57.5Hz 62.5Hz
11. Resolution: tgδ: 0.1% Cx: 0.1pF
12. Accuracy △tgδ: ±(reading * 1.0% + 0.040%). △Cx: ±(reading * 1.0% + 1pF)
13. Measurement range tgδ: No limit
Cx 15pF
10KV Cx = (Cx1 + Cx2 + Cx3 + Cx4) <60 nF
5KV Cx = (Cx1 + Cx2 + Cx3 + Cx4) <150 nF
1KV Cx = (Cx1 + Cx2 + Cx3 + Cx4) <300 nF
CVT test Cx = (Cx1 + Cx2 + Cx3 + Cx4) <300 nF
14. LCR measurement range: Inductance L > 20H (2kV), Resistance R > 10KΩ (2kV)
15. LCR measurement accuracy: 1% angular resolution 0.01
16. CVT ratio range: 10-10000
17. CVT ratio accuracy: 1% CVT ratio resolution: 0.01
18. Memory size: Supports USB flash drive data storage
Media analyzer, tanδ test kit, dielectric loss tester, dielectric loss test kit
Send Inquiry to This Supplier
You May Also Like
-
MS-100D, Transformer Turns Ratio TesterNegotiableMOQ: 1 Combo
-
MS-100ES, Handheld Three-Phase Turns Ratio TesterNegotiableMOQ: 1 Combo
-
MS-100B(E), Transformer Turns Ratio TesterNegotiableMOQ: 1 Combo
-
MS-207T, Transformer Load Switch TesterNegotiableMOQ: 1 Combo
-
MS-510R, Transformer Winding Resistance TesterNegotiableMOQ: 1 Combo
-
MS-510S, Transformer DC Resistance TesterNegotiableMOQ: 1 Combo
-
MS-520, DC Resistance TesterNegotiableMOQ: 1 Combo
-
MS-520S, Three-Channel DC Resistance TesterNegotiableMOQ: 1 Combo
-
MS-101G1, Dielectric Loss TesterNegotiableMOQ: 1 Combo
-
MS-401, SF6 Gas Density Relay CalibratorNegotiableMOQ: 1 Combo