1.Summary
ZBW series combined power distribution station is the power distribution equipment combining high voltage transformer.transformer and low voltage equipment that is used for city tall buildings urban&rural buildings,residence communities,medium&small factories,mines,oil fields and temporary electrical power consuming sites. The station function to receive and distribute power energy in power distribution system.
ZBW series combined transformer features compact structure,package unit,safe and reliable operation,convenient maintenance,attractive apperance,bigh mobility and small size.It can be used as loop network power distribution system.It is a new set of equipment for urban&rural transformer substation construction and drenovation.
ZBW series combined substation complies with the standards of GB/T17467-1998 High Voltage/Low Voltage Pre-Installed Transformer substation and IEC1330.
2.Technical Parameters

2.1 High Voltage Switch Panel Parameter Table

 

Series No

Name

Unit

Parameter

1

Nominal voltage

kV

12

2

Nominal frequency

Hz

50

3

Nominal current

A

630

4

Nominalshort withstanding current

kA/2S

20

5

Nominal short peak current

kA

50

6

Withstanding current when grounding switch is closed for a short time

kA/2S

20

7

Peak current when grounding switch is closed for a short time

kA

50

8

5% nominal on/off current

A

31.5

9

Nominal load on/off current

A

630

10

Drifting current

A

1400

11

Idle transformer on/off current

A

16

12

Fuse combination switch short-circuit on/off current

kA/2S

20

13

On/off current

kA

50

14

1 min power frequency withstand voltage ground,inter-phase/isolation notch

kV effective value

42/48

15

Impulse withstand voltage ground,inter-phase/isolation notch

kV effective value

75/85

2.2 Transformer Main Technical Parameter Table

 

Type

Nominal voltage(Kv)

Nominal capacitance(kVA)

S9-M, S11-M

6,10

50-1600

SC9  SC10  SG10

6,10

50-1600

2.3 Fuse Parameter Table

 

Type

Nominal voltage(kV)

Nominal on/off current(kA)

Fuse nominal current(A)

Fuse specific current(A)

SFLDJ

SFLAJ

   12

31.5

40

6.3 10 16 20 25 31.5 40

100

50 63 80 100

125

125

40

200

160 200

Send Inquiry to This Supplier

Message
0/5000

Want the best price? Post an RFQ now!
Business Type
Trading Company
Year Established
2001
Total Employees
101 - 200 People
Main Markets
North America, South America, Eastern Europe

Recommended Categories

Explore top categories and find suppliers for your specific needs