Home > Construction & Decoration > Prefabricated Building > Prefabricated Hotel > High Accurate Megger Digital Insulation Tester Max 5T Ohm , Auto Calculate PI and DARt YH510

High Accurate Megger Digital Insulation Tester Max 5T Ohm , Auto Calculate PI and DARt YH510

High Accurate Megger Digital Insulation Tester Max 5T Ohm , Auto Calculate PI and DARt YH510 photo-1
Negotiable MOQ: 1 Unit (Price negotiable depending on order volume and customization)
Key Specifications
Get Latest Price
Brand Name:
HAODI
Place of Origin:
China
Model Number:
YH 510
Payment & Shipping
Payment Methods:
Port of Shipment:
China
Delivery Detail:
7 days
Brand Name HAODI
Place of Origin China
Model Number YH 510
Delivery Time:7-15days
Certification:ISO

High Accurate Megger Digital Insulation Tester Max 5T Ohm , Auto Calculate PI and DARt YH510

Quick Detail:

☉Test Voltage from 250V~5000V

☉Insulation Resistance up to 5TΩ

☉ Short Current up to 3mA

☉ Auto Calculate PI(Polarization Index) and DAR(Dielectric absorption ratio)

☉ Step-Voltage Measurement

☉ Temperature measurement

☉ Temperature compensation for insulation Test

Features

High Voltage Digital Insulation Tester YH510

☉ Checking the insulation of high-voltage electrical equipment

 (electric motor,  transformer,  and cable,  etc)

☉Test Voltage from 250V~5000V

☉Insulation Resistance up to 5TΩ

☉ Short Current up to 3mA

☉ Auto Calculate PI(Polarization Index) and DAR(Dielectric absorption ratio)

☉ Step-Voltage Measurement

☉ Temperature measurement

☉ Temperature compensation for insulation Test

☉ Leakage Current measurement

☉ Data Storage function and uploading to PC by USB2.0 interface

☉ Power Supply:LR6 Battery×6/ rechargeable battery Ni~MH 7.2V 

(Charger;Input Voltage 100V~240V ; Frequency 50Hz~60Hz,  Output Voltage 12V DC 3A)

☉ Timer Function

☉Weight 2.5kg (not including Battery)

☉Size 284mm(L)×230mm(w)×125mm(H)

Test Voltage

☉ Test Voltage Range; DC250V~ DC 5.00kv

☉ Voltage Set:

☉ Wide adjust;(250V; 500V; 1000V; 2.5kv; 5kv)

☉ Fine adjust (250V~1KV; Step 25V; 1KV~5KV,  Step 100V)

☉ Accuracy; 5%

☉ Step mode:500V,  1.0KV,  1.5KV,  2.0KV,  2.5KV

☉ Test Current 1nA~3mA

Temperature compensation

For obtaining the insulation resistance under a temperature other than current ambient temperature.

Converts the measured value of resistance to the insulation resistance under a reference temperature,  and displays the result.

Depending on the different properties of test objects,  there are 10 modes of compensation.

Insulation Resistance  

Set test voltage 

    Test range 

Threshold value of basic error

250 V DC 

0.01 MΩ ~ 2.5 GΩ 

  ±(5% rdg + 5 dgt) 

2.51 GΩ ~ 250 GΩ 

  ±(20% rdg +10 dgt) 

500 V DC 

0.01 MΩ ~ 5.0 GΩ 

  ±(5% rdg +5 dgt) 

5.01 GΩ ~ 500 GΩ 

  ±(20% rdg +10 dgt) 

1000 V DC 

0.01 MΩ ~ 10 GΩ 

  ±(5% rdg +5 dgt) 

10.1 GΩ ~ 500 GΩ 

  ±(20% rdg +10 dgt) 

501 GΩ ~ 999 GΩ 

  ±(30% rdg +20 dgt) 

2.5 kV DC 

0.01 MΩ ~ 25 GΩ 

  ±(5% rdg +5 dgt) 

25.1 GΩ ~ 500 GΩ 

  ±(20% rdg +10 dgt) 

501 GΩ ~ 999 GΩ 

  ±(30% rdg +20 dgt) 

1 TΩ ~ 2.5 TΩ 

  ±(30% rdg + 40 dgt)

5 kV DC 

0.01 MΩ ~ 50 GΩ 

  ± (5% rdg + 5 dgt)

50.1 GΩ ~ 500 GΩ 

  ±(20% rdg + 10 dgt)

501 GΩ ~ 999 GΩ 

  ±(30% rdg + 20 dgt)

1 TΩ ~ 5 TΩ 

  ±(30% rdg + 40 dgt)

Leak Current

  Range 

  Measuring range 

Threshold value of basic error 

10 nA 

1.00 nA ~ 9.99 nA 